Liebert 30-130kVA Operation And Maintenance Manual page 90

30-130kva, 60hz, single module system
Table of Contents

Advertisement

Table 7
Alarms, functions, and corrective actions (continued)
Actual
Alarm/fault
Name
Displayed
Description
On Front
of Alarm/
Panel
Fault
SBS Ovld
SBS Overload
Phase A
Phase A
SBS Ovld
SBS Overload
Phase B
Phase B
SBS Ovld
SBS Overload
Phase C
Phase C
Inverter I
Inverter
Limit
Current Limit
Output OF/UF Output OF/UF
Inverter
Inv Ovld
Overload
Phase A
Phase A
Inverter
Inv Ovld
Overload
Phase B
Phase B
Fault
Or
Latch
Dial
Freeze
Alarm
Mask
Mask
Mask
Alarm
NO
NO
Alarm
NO
NO
Alarm
NO
NO
Alarm
NO
NO
Alarm
NO
YES
Alarm
NO
YES
Alarm
NO
YES
Event Log
Mask
Meaning and Corrective Action(s)
With the load on Static Bypass, the phase A
output kVA or kW or RMS current has
exceeded 115% of the nominal per-phase
kVA or kW or RMS current rating. The UPS
NO
YES
will show time remaining until a shutdown
will occur, per the Overload vs. time curve.
The alarm will clear when the overload falls
to below 110% of the rating.
With the load on Static Bypass, the phase B
output kVA or kW or RMS current has
exceeded 115% of the nominal per-phase
kVA or kW or RMS current rating. The UPS
NO
YES
will show time remaining until a shutdown
will occur, per the Overload vs. time curve.
The alarm will clear when the overload falls
to below 110% of the rating.
With the load on Static Bypass, the phase C
output kVA or kW or RMS current has
exceeded 115% of the nominal per-phase
kVA or kW or RMS current rating. The UPS
NO
YES
will show time remaining until a shutdown
will occur, per the Overload vs. time curve.
The alarm will clear when the overload falls
to below 110% of the rating.
The instantaneous inverter current of any
one phase has exceeded its pulse-by-pulse
NO
YES
current limit value. The UPS will shutdown
when the Current Overload vs. time curve is
exceeded.
Output frequency differs from the nominal
(60Hz) by more than 0.5Hz. No transfer or
NO
YES
shutdown occurs. Contact Liebert Global
Services at once.
With the load on UPS, Phase x output KVA
or KW or RMS current has exceeded 105%
of the nominal per phase rating. The UPS
will begin sending the time remaining until a
NO
YES
transfer or shutdown will occur, per the
Overload vs. Time Curve. The alarm
condition will clear when the overload
returns to below the nominal rating.
With the load on UPS, Phase A output kVA
or kW or RMS current has exceeded 105%
of the nominal per phase rating. The UPS
will begin sending the time remaining until a
NO
YES
transfer or shutdown will occur, per the
Overload vs. Time Curve. The alarm
condition will clear when the overload
returns to below the nominal rating.
82