Termination Location And Vent Information; Vent Termination Minimum Clearances - Harman P43 Installation Manual

Harman p43; p61a; p68 freestanding pellet stove
Table of Contents

Advertisement

4

Termination Location and Vent Information

A. Vent Termination Minimum Clearances
Figure 4.1
Figure 4.2
11
3 Ft.
to
Combustibles
3 Ft.
to Combustibles
3 Ft.
to
Combustibles
3 Ft.
to Combustibles
Harman® • P-Series Installation Manual_R8 • 2014 - ___ • 04/15
INSTALL VENT AT CLEARANCES SPECIFIED BY THE
VENT MANUFACTURER
#1 Preferred method
(Figure 4.1)
This method provides excellent venting for normal operation
and allows the stove to be installed closest to the wall. Two
inches from the wall is safe; however, four inches allows
better access to remove the rear panel. The vertical portion of
the vent should be three to five feet high. This vertical section
will help provide natural draft in the event of a power failure.
Seal pipe joints with silicone or aluminum tape in addition to
the sealing system used by the manufacturer.
Do not place joints within wall pass-through.
#2 Preferred method
(Figure 4.2)
This method also provides excellent venting for normal
operation but requires the stove to be installed farther from
the wall. The vertical portion of the vent should be three to
five feet high and at least 1" from a combustible wall. This
vertical section will provide natural draft in the event of a
power failure.
Seal pipe joints with silicone or aluminum tape in addition to
the sealing system used by the manufacturer.
If the stove is installed below grade be sure the vent
termination is at least 12" above grade. The outlet must also
be 1 foot from the house/building.
Do not place joints within wall pass-through.
!
Keep combustible materials (such as grass, leaves,
etc.) at least 3 feet away from the flue outlet on the
outside of the building.
CAUTION
3-90-436168i