Electrical And Performance Data - York PC9B12N060UP11 Technical Manual

Gas-fired condensing / high efficiency upflow modulating furnaces with ecm motors natural gas 60 - 120 mbh input
Hide thumbs Also See for PC9B12N060UP11:
Table of Contents

Advertisement

ELECTRICAL AND PERFORMANCE DATA

Input
Max/Min
Models
MBH
PC9B12N060UP11
60/21
PC9B12N080UP11
80/28
PC9C16N080UP11
80/28
PC9C16N100UP11
100/35
PC9C20N100UP11
100/35
PC9D20N120UP11
120/42
Max. Outlet
Air Temp.
Models
°F
PC9B12N060UP11
170
PC9B12N080UP11
170
PC9C16N080UP11
170
PC9C16N100UP11
170
PC9C20N100UP11
170
PC9D20N120UP11
170
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
The furnace shall be installed so that the electrical components are protected from water.
NOTES:
1. Wire size based on copper conductors, 60°C, 3% voltage drop.
2. Continuous return air temperature must not be below 55°F.
3. Air flows above 1800 CFM require either return from two sides or one side plus bottom.
Unitary Products Group
Output
Blower Size
Max/Min
MBH
In.
57/20
11 x 8
76/26
11 x 8
76/26
11 x 10
95/33
11 x 10
95/33
11 x 11
115/39
11 x 11
Nominal
Cabinet Width Total Unit AFUE
Airflow
CFM
In.
Amps
1200
17-1/2
1200
17-1/2
1600
21
1600
21
2000
21
2000
24-1/2
Max.
Blower
Over-current
Protect
HP
Amps
1/2
7.7
20
1/2
7.7
20
3/4
9.6
20
3/4
9.6
20
1
12.8
20
1
12.8
20
Min. Wire Size
(awg) @ 75 ft.
One Way
%
9
95.0
14
9
95.0
14
12
95.0
14
12
95.0
14
14
95.0
12
14
95.0
12
246813-YTG-C-0606
Air Temp. Rise
Air Temp. Rise
Maximum Input
Minimum Input
°F
°F
40 - 70
20 - 50
40 - 70
20 - 50
40 - 70
20 - 50
40 - 70
20 - 50
40 - 70
20 - 50
40 - 70
20 - 50
Approximate
Operating Weight
135
142
157
162
164
180
3