Air Flow Data; Jumper Settings - York PC9B12N060UP11 Technical Manual

Gas-fired condensing / high efficiency upflow modulating furnaces with ecm motors natural gas 60 - 120 mbh input
Hide thumbs Also See for PC9B12N060UP11:
Table of Contents

Advertisement

246813-YTG-C-0606

AIR FLOW DATA

PC9B12N060UP11
CFM
High
Low
1330
900
1130
800
1220
850
1040
730
1120
770
920
650
950
660
740
540
860
610
690
540
790
570
630
530
PC9C16N080UP11
PC9C16N100UP11
CFM
High
Low
1660
1110
1550
1050
1610
1070
1440
960
1470
990
1370
920
1290
850
1130
790
1230
850
1050
720
1110
760
950
660
PC9D20N120UP11
CFM
High
Low
2280
1510
1860
1190
2090
1370
1630
1060
1880
1250
1620
1030
1500
960
1410
880
1490
920
1290
790
1360
840
1140
690
All CFM's are shown at 0.5" w.c. external static pressure.These units have variable speed motors that automatically adjust to provide constant CFM from 0.0" to 0.6" w.c.
static pressure. From 0.6" to 1.0" static pressure, CFM is reduced by 2% per 0.1" increase in static. Operation on duct systems with greater than 1.0" w.c. external static
pressure is not recommended.
NOTE: At some settings, LOW COOL airflow may be lower that what is required to operate an airflow switch on certain models of electronic air cleaners. Consult the
instructions for the electronic air cleaner for further details.
NOTES:
1. Airflow expressed in standard cubic feet per minute (CFM) and in cubic meters per minute (m
2. Return air is through side opposite motor (left side).
3. In order to stay within the velocity rating the filters, airflows above 1800 CFM (50.97 m
6
HIGH / LOW SPEED COOLING AND HEAT PUMP CFM
m³/min
High
Low
High
37.7
25.5
1310
32.0
22.7
1100
34.6
24.1
1220
29.4
20.7
1000
31.7
21.8
1090
26.1
18.4
900
26.9
18.7
880
21.0
15.3
680
24.4
17.3
810
19.5
15.3
630
22.4
16.1
730
17.8
15.0
590
m³/min
High
Low
High
47.0
31.4
2210
43.9
29.7
1780
45.6
30.3
2040
40.8
27.2
1620
41.6
28.0
1840
38.8
26.1
1560
36.5
24.1
1470
32.0
22.4
1370
34.8
24.1
1460
29.7
20.4
1250
31.4
21.5
1310
26.9
18.7
1090
m³/min
High
Low
64.6
42.8
52.7
33.7
59.2
38.8
46.2
30.0
53.2
35.4
45.9
29.2
42.5
27.2
39.9
24.9
42.2
26.1
36.5
22.4
38.5
23.8
32.3
19.5
PC9B12N080UP11
CFM
m³/min
Low
High
890
37.1
740
31.2
830
34.6
670
28.3
720
30.9
610
25.5
610
24.1
510
19.3
580
22.9
500
17.8
530
20.7
500
16.7
PC9C20N100UP11
CFM
m³/min
Low
High
1480
62.6
1180
50.4
1350
57.8
1050
45.9
1250
52.1
1010
44.2
940
41.6
890
38.8
930
41.3
790
35.4
810
37.1
690
30.9
3
/min).
3
/min) require either return from two sides or one side plus bottom.

JUMPER SETTINGS

Low
COOL Tap
ADJ Tap
25.2
A
21.0
B
23.5
A
19.0
B
20.4
A
17.3
C
17.3
B
14.4
D
16.4
C
14.2
D
15.0
C
14.2
D
JUMPER SETTINGS
Low
COOL Tap
ADJ Tap
41.9
A
33.4
B
38.2
A
29.7
B
35.4
A
28.6
C
26.6
B
25.2
D
26.3
C
22.4
D
22.9
C
19.5
D
JUMPER SETTINGS
COOL Tap
ADJ Tap
A
B
A
B
A
C
B
D
C
D
C
D
Unitary Products Group
B
B
A
A
C
B
C
B
A
A
C
C
B
B
A
A
C
B
C
B
A
A
C
C
B
B
A
A
C
B
C
B
A
A
C
C

Advertisement

Table of Contents
loading

Table of Contents