Piping Length/Additional Refrigerant Volume
6.4
The amount of refrigerant put into the outdoor unit at the factory is sufficient to fill up to 20m of
!
refrigerant pipework.
If the length of the refrigerant pipework is 20m or less, addition of refrigerant at the installation site
!
is unnecessary.
If the length of the pipework exceeds 20m, extra refrigerant must be added. Refer to the table
!
below for details of the extra amounts.
Overcharge or undercharge of refrigerant in the outdoor unit will cause malfunction of
!
the compressor.
The prescribed amount of the replenishment of the refrigerant is shown in the table below:
Additional amount of refrigerant to add at
MODEL
Less
than
(RAV-)
20m
134A-PE
164A-PE
264A/A8-PE
364A8-PE
464A8-PE
6. PERFORMANCE CHARACTERISTICS
±
installation site (kg)
50g
Less
Less
Less
Less
than
than
than
than
25m
30m
35m
40m
0.18
0.35
Ñ
Ñ
0.18
0.35
Ñ
Ñ
0.18
0.35
Ñ
Ñ
0.18
0.35
0.53
0.7
0.25
0.5
0.75
1.0
!
ADD ONLY R407C REFRIGERANT TO THESE UNITS
Less
Less
Less
Less
Less
than
than
than
than
than
45m
50m
5m
20m
25m
Ñ
Ñ
0.79
1.05
1.23
Ñ
Ñ
0.94
1.2
1.38
Ñ
Ñ
1.64
1.9
2.08
0.88
1.05
2.44
2.7
2.88
1.25
1.5
3.13
3.5
3.75
48
Recharge amount if unit is reclaimed
±
(kg)
50g
Less
Less
Less
Less
than
than
than
than
30m
35m
40m
45m
1.4
Ñ
Ñ
Ñ
1.55
Ñ
Ñ
Ñ
2.25
Ñ
Ñ
Ñ
3.05
3.23
3.4
3.58
4.0
4.25
4.5
4.75
Less
than
50m
Ñ
Ñ
Ñ
3.75
5.0