Indoor Unit Connection Check Procedure - Fujitsu Airstage J-II Service Manual

Small vrf system
Hide thumbs Also See for Airstage J-II:
Table of Contents

Advertisement

1-2-5 Indoor unit connection check
Please perform the indoor unit connection check according to following procedures.
Turn on the power
of indoor unit and
outdoor unit.
LED105
LED104
MODE/EXIT
SELECT
SELECT
ENTER
SELECT
ENTER
Press the
more than 3 seconds.
This will be displayed when the
Indoor unit connection check
starts.
SWITCH POSITION
Set to Function mode [F3].
(When [F4] to [F9] are displayed,
continue to press the "SELECT"
button until [F3] is displayed.)
Press the "SELECT" button until
"12" is displayed.
button for
"ENTER"
When indoor unit connection check
can not be performed
Outdoor unit printed circuit board
ENTER
MODE/EXIT
01-08
POWER
ERROR
MODE
LED101
LED102
(GREEN)
(RED)
LED105
LED104
MODE
SELECT
ENTER
/EXIT
SW107
SW108
SW109
(*1)
Confirm the number of connected indoor
units and the volume ratio of the indoor
units connection.
(*1) The number of connected
indoor units
SELECT
Ex.) When 8 units are connected
(*2)
(*2) Volume ratio of the indoor
units connection
Ex.) When the ratio is 120%
Exit indoor unit connection check
ENTER
mode.
When error occurs
Please refer to the following "Error code"
for details
ENTER
[ Note ] Error code
22.1: Connecting Indoor units capacity error
24.2: Connecting number of indoor unit error
26.1: Dual address number is existing
Other Error code: Refer to the Trouble shooting
When it finishes normally, nothing will be displayed on
7 segment display.
7 Segment
LED Lamp
Push button switch