Classification
Install
Push switch
on outdoor unit PCB
Setting mode
[ F2 ]
Correction
Change of
function 1
Change of
function 2
Low noise
setting 1
Change of
function 3
Change of
function 4
ITEM
Setting Mode
CODE No.
00
Pipe length setting
10
Sequential start shift
Setting is forbidden
Cooling capacity shift
11
Heating capacity shift
12
13
Defrost setting shift
14
Pressure equalization time shift
before defrosting start
20
Switching between forced stop or
emergency stop
21
Operation mode selecting method
22
Snow falling protection fan mode
Setting is forbidden
23
Interval setting for snow falling
protection fan mode
Setting is forbidden
24
High static pressure mode
Setting is forbidden
25
Oil recovery
Setting is forbidden
Oil recovery Abnormal
26
low pressure protection control
Setting is forbidden
27
Error code Notification
28
Change of unit (Temperature)
29
Change of unit (Pressure)
30
Energy saving level setting
31
Heating Starting prosess
Setting is forbidden
40
Capacity priority setting
(in low noise mode)
41
Low noise mode setting
42
Low noise mode operation level
Setting is forbidden
60
Back up operation
Setting is forbidden
70
Electricity meter No. setting 1
(Set the ones digit and tens digit of the No of
the electricity meter connected to CN135.) *3
71
Electricity meter No. setting 2
(Set the hundreds digit of the No. of the
electricity meter connected to CN135.) *3
72
Electricity meter pulse setting 1
(Set the ones digit and tens digit of the No. of
the electricity meter pulse setting connected
to CN135.) *4
73
Electricity meter pulse setting 2
(Set the hundreds digit and thousands digit
of the electricity meter pulse setting connected
to CN135.) *4
*3 : When electricity meter No. is set to "000" and "201 to 299", the pulses input to CN135 become ineffective.
Available setting number is "001" to "200"
*4 : When the electricity meter pulse setting is set to "0000", the pulses input to CN135 become ineffective.
Available setting number is "0001" to "9999"
Setting is forbidden: Any of problems caused by changing these setting is not covered by the warranty.
Only for solution : Only when the refrigerant noise during Defrosting was pointed out. It is the case that the
ITEM
CODE No.
00
40-65m
01
0-40m
02
65-90m
03
90-120m
Setting is forbidden
04
00
Standard
01
02
03
00
Normal mode
01
Save energy mode 1 (+2 °C )
02
High power mode 1 (-2 °C )
03
High power mode 2 (-4 °C )
04
High power mode 3 (-5 °C )
00
Normal mode
01
Save energy mode (-2 °C )
02
High power mode 1 (+2 °C )
03
High power mode 2 (+4 °C )
00
End temperature:Normal
01
End temperature:Higher
00
No time shift
01
Shift 1 ( 30 sec.)
02
Shift 2 ( 60 sec.)
03
Shift 3 ( 90 sec.)
04
Shift 3 ( 120 sec.)
00
Forced stop
01
Emergency stop
00
Priority given to the first command
01
Priority given to the external input of outdoor unit
02
Priority given to the master indoor unit
00
Normal operation
01
00
Standard
01
02
03
00
Standard
01
02
Standard
00
01
02
03
00
Standard
01
00
Enable
01
Disable
00
Celsius( °C )
01
Fahrenheit ( F)
00
MPa
01
psi
00
Level 1 (stop)
01
Level 2 (operated at 40% capacity)
02
Level 3 (operated at 60% capacity)
03
Level 4 (operated at 80% capacity)
04
Level 5 (operated at 100% capacity)
00
Standard
01
00
Off (quiet priority)
01
On (capacity priority)
00
Off (Normal)
01
On (Low noise mode operation is always done)
00
Standard (47dB)
01
00
Standard
01
00~99
Setting number x00~x99
( Refer to Design & Technical Manual for details.)
00~02
Setting number 0xx~2xx
( Refer to Design & Technical Manual for details.)
00~99
Setting number xx00~xx99
( Refer to Design & Technical Manual for details.)
00~99
Setting number 00xx~99xx
( Refer to Design & Technical Manual for details.)
compressor operating time in heating will be shorter.
01-16
Setting Function
Only for solution
Default
00
00
00
00