Discharge Pressure Sensor Error - Fujitsu Airstage J-II Service Manual

Small vrf system
Hide thumbs Also See for Airstage J-II:
Table of Contents

Advertisement

Trouble shooting 31
OUTDOOR UNIT Error Method:

Discharge Pressure Sensor Error

Detective Actuators:
Discharge pressure sensor
Forecast of Cause :
1. Discharge pressure sensor connector disconnection, open
2. Discharge pressure sensor defective
3. Main PCB defective
Check Point 1 : Check the discharge pressure sensor connection state
Connector connection state check
Cable open check
OK
Check Point 2 : Check the discharge pressure sensor
Sensor characteristics check
* For the characteristics of the discharge pressure sensor,
refer to the "Service Parts Information 20".
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN118:1-3) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
Discharge pressure sensor (CN118:1-3)
Indicate or Display:
Outdoor Unit : E. 86. 1
Indoor Unit
Error Code
Detective details:
When any of the following conditions is satisfied, a discharge pressure
sensor error is generated.
1. 30 seconds or more have elapsed since the outdoor unit power was turned
on and pressure sensor detected value
or more
2. 30 seconds or more have elapsed since the outdoor unit power was turned
on and pressure sensor detected value
PS
1 2 3
1 2 3
CN118
: Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
: 86
DC
04-41
0.3V continued for 30 seconds
5.0V was detected.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Airstage j-iis

Table of Contents