Check Point : ARXC36LATH (High Static Pressure Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
150°C
Pr
Check Point : ARXC45/ 60LATH (High Static Pressure Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
145°C
Pr
Check Point : ARXC72LATH (High Static Pressure Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
145°C
Pr
Check Point : ARXC90LATH (High Static Pressure Duct Type)
Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
145°C
Pr
BLUE (Low)
VIOLET (Med)
RED (Hi)
(AC)
BLACK
WHITE
BLUE (Low)
VIOLET (Med)
RED (Hi)
(AC)
BLACK
WHITE
BLUE (S-Lo)
VIOLET (Low)
PINK (Med)
RED (Hi)
BLACK
(AC)
WHITE
BLUE (S-Lo)
VIOLET (Low)
PINK (Med)
RED (Hi)
(AC)
BLACK
WHITE
04-102
Lead wire
Resistance value
White Red
13.4
Red
Black
16.9
Red
Violet
11.5
Violet
Blue
13.3
Lead wire
Resistance value
White Red
6.84
Red
Black
9.78
Red
Violet
6.1
Violet
Blue
6.1
Lead wire
Resistance value
White Red
5.25
Red
Black
5.02
Red
Pink
1.86
Pink
Violet
0.94
Violet
Blue
0.94
Lead wire
Resistance value
White Red
4.24
4.16
Red
Black
0.46
Red
Pink
Pink
Violet
0.91
Violet
Blue
0.46
8%
8%
8%
8%
at 20°C
7%
7%
7%
7%
at 20°C
7%
7%
7%
7%
7%
at 20°C
7%
7%
7%
7%
7%
at 20°C