Delivered Condition; Vitotronic 200, Type Kw5, Part No. 7186 317; Specification - Viessmann VITOGAS Technical Manual

Low temperature gas boiler 11 to 60 kw
Table of Contents

Advertisement

Control units
(cont.)
Permissible ambient temperature
– during operation
– during storage and transport
Rated capacity of the relay outputs
Heating circuit pumps
sA
Circulation pump for cylinder heat-
ing
sK
DHW circulation pump
Total sÖ, sA, sK, gS
fA
Burner
Burner, two-stage
Only with auxiliary module (part of the
standard delivery for Viessmann boil-
ers)
Total

Delivered condition

■ Programming unit
■ Outside temperature sensor
■ Boiler water temperature sensor
■ Cylinder temperature sensor
■ Bag with technical documentation
Heating system with DHW cylinder
Order the circulation pump with check valve for cylinder temperature
control separately.

6.7 Vitotronic 200, type KW5, part no. 7186 317

Specification

Composition
The control unit comprises a standard unit, electronic modules and a
programming unit.
Standard unit:
■ ON/OFF switch
■ Terminals for high limit safety cut-out test
■ Keys for emissions test function
■ Optolink laptop interface
■ Temperature controller
DIN TR 96808
or
DIN TR 116807
■ High limit safety cut-out
DIN STB 106005
or
DIN STB 98108
or
DIN STB 116907
■ Operation and fault displays
■ Plug connection chamber
– Connection of external equipment via a system plug
– Connection of three-phase consumers via additional contactors
Programming unit:
■ With digital time switch
■ Backlit display with plain text user prompts
■ Adjustment and display of temperatures and codes
■ Fault message display
VITOGAS
0 to +40 °C
Installation in living
spaces or boiler rooms
(standard ambient con-
ditions)
−20 to +65 °C
4(2) A, 230 V~
4(2) A, 230 V~
4(2) A, 230 V~
max. 4 A, 230 V~
4(2) A, 230 V~
1(0.5) A,230 V~
max. 6 A, 230 V~
Heating system with heating circuit with mixer
An extension kit (accessories) is required for each heating circuit with
mixer.
■ Rotary selector for the temperature in standard mode
■ Keys:
– Temperature for reduced mode
– Program selection
– Holiday program
– Party and economy mode
– DHW temperature
– Heating curves for boiler water temperature and flow temperature
– Heating circuit selection
– Time / Date
Functions
■ Weather-compensated control of the boiler water and/or flow tem-
perature
■ Electronic maximum and minimum temperature limit
■ Demand-dependent heating circuit pump and burner stop (not for
burners on boilers with a low-end boiler water temperature limit)
■ Adjustment of a variable heating limit
■ Anti-seizing pump protection
■ Integral diagnostic system
■ Flue gas temperature monitoring with flue gas temperature sensor
■ Maintenance display
■ Adaptive cylinder temperature control with priority control (heating
circuit pumps off, mixer closed)
■ Auxiliary function for DHW heating (short-term heating to a higher
temperature)
■ Optimised control of a heating circuit, e.g. underfloor heating circuit,
via a flow and return temperature sensor
■ Screed drying, for underfloor heating systems