4-5. Outdoor Unit (RAS-18NA-E, RAS-18N2AX)

No.
Parts name
1
Compressor
2
Fan motor (for outdoor)
Running capacitor
3
(for fan motor)
Running capacitor
4
(for compressor)
5
Magnetic contactor
Type
Output (Rated) 1500 W, 2 poles, 1 phase, 220 – 240 V, 50 Hz
PH340X3C-4KT1
Winding resistance (Ω)
(at 20°C)
Output (Rated) 42 W, 6 poles, 1 phase, 220 – 240 V, 50 Hz
WLF-240-42A-1
Winding resistance (Ω)
(at 20°C)
451205L
AC 450 V, 2.0µF
RS44B506U0218S AC 440 V, 50µF
CLK-26J
220 – 240 V, 50 Hz
− 14 −
FILE NO. SVM-06005
Specifications
C-R
1.46
Red-Black
188
C-S
2.47
White-Black
289