<When the installation plate is directly mounted on
the wall>
1. Securely fit the installation plate onto the wall by
screwing it in the upper and lower parts to hook up
the indoor unit.
2. To mount the installation plate on a concrete wall
with anchor bolts, utilize the anchor bolt holes as
illustrated in the above figure.
3. Install the installation plate horizontally in the wall.
CAUTION
When installing the installation plate with a
mounting screw, do not use the anchor bolt hole.
Otherwise the unit may fall down and result in
personal injury and property damage.
Installation plate
<Keep horizontal direction>
5 mm dia. hole
Clip anchor
(local parts)
Fig. 8-4-4
CAUTION
Failure to firmly install the unit may result in
personal injury and property damage if the unit falls.
• In case of block, brick, concrete or similar type
walls, make 5 mm dia. holes in the wall.
• Insert clip anchors for appropriate 7 mounting screws.
NOTE
• Secure four corners and lower parts of the
installation plate with 6 to 7 mounting screws to
install it.
8-4-3. Electrical work
1. The supply voltage must be the same as the rated
2. Prepare the power source for exclusive use with the
NOTE
• Wire type : More than 1.5 mm
Anchor
NOTE
bolt
• Perform wiring works so as to allow a generous
Projection
15 mm or less
7 Mounting
screw
∅4 x 25 s s s s s
– 38 –
FILE NO. SVM-06005
voltage of the air conditioner.
air conditioner.
245 IEC66) or 1.3 mm
CAUTION
• This appliance can be connected to the mains in
the following way.
Connection to fixed wiring:
A switch or circuit breaker which disconnects all
poles and has a contact separation of at least
3 mm must be incorporate in the fixed wiring. An
approved circuit breaker or switches must used.
wiring capacity.
2
(H07RN-F or
2
(AWG-16)