8-7. Others

8-7-1. Gas leak test
B
Valve stem cap connection
• Check the flare nut connections, valve stem cap connections and
service port cap connection for gas leak with a leak detector or
soap water.
• Check the flare nut connections, valve stem cap
connections and service port cap connections for
gas leak with a leak detector or soap water.
8-7-2. Test operation
To switch the TEST RUN (COOL) mode, press
TEMPORARY button for 10 sec.
(The beeper will make a short beep.)
TEMPORARY button
Flare nut connections
(Indoor unit)
Flare nut connections
(Outdoor unit)
A
Valve stem cap connection
Service port cap connection
Fig. 8-7-1
Fig. 8-7-2
8-7-3. Auto restart setting
This product is designed so that, after a power failure,
it can restart automatically in the same operating mode
as before the power failure.
Information
The product was shipped with Auto Restart function
in the off position. Turn it on as required.
<How to set the auto restart>
• Press and hold the TEMPORARY button for about
3 seconds. After 3 seconds, the electronic beeper
makes three short beeps to tell you the Auto
Restart has been selected.
• To cancel the Auto Restart, follow the steps
described in the section Auto Restart Function of
the Owner's Manual.
– 46–
FILE NO. SVM-06005