Carrier 58MEB Installation, Start-Up, And Operating Instructions Manual page 29

Deluxe 4---way multipoise fixed ---capacity condensing gas furnace sizes 040---120, series 100
Hide thumbs Also See for 58MEB:
Table of Contents

Advertisement

WARNING
!
FIRE HAZARD
Failure to follow this warning could result in personal injury,
death, or property damage.
Do not connect aluminum wire between disconnect switch
furnace. Use only copper wire. (See Fig. 32.)
WARNING
!
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in serious injury,
death, or property damage.
The cabinet MUST have an uninterrupted or unbroken ground
according to NEC ANSI/NFPA 70-2008 and Canadian
Electrical Code CSA C22.1 or local codes to minimize
personal injury if an electrical fault should occur. This may
consist of electrical wire or conduit approved for electrical
ground when installed in accordance with existing electrical
codes. Do not use gas piping as an electrical ground.
Factory Installed J-Box Location
Install electrical entry hole filler plugs (factory-supplied in loose
parts bag) in unused power entry holes. (See Fig. 33.)
J-Box Relocation
1. Remove 2 screws holding auxiliary J-box. (See Fig. 34.)
2. Rotate J-box 180° and attach box to left side, using
holes provided.
3. Install electrical entry hole filler plugs (factory-supplied
loose parts Bag) in unused power entry holes.
(See Fig. 34.)
POWER ENTRY HOLE
FILLER PLUG (FACTORY-
SUPPLIED LOOSE PARTS BAG)
UNUSED 7/8-IN. (22 mm) DIAMETER
POWER ENTRY HOLES
ALTERNATE
FIELD
LOCATION
Fig. 34 - - Relocating J-Box
POWER ENTRY HOLE
FILLER PLUG (FACTORY-
SUPPLIED LOOSE PARTS BAG)
Fig. 33 - - Factory Installed J-Box Location
WARNING
!
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal injury,
and death, or property damage.
If manual disconnect switch is to be mounted on furnace,
select a location where a drill or fastener will not contact
electrical or gas components.
24–V WIRING
Connect 24-v thermostat leads to 24-v terminal block on furnace
control. For proper cooling operation, Y wire from thermostat
MUST be connected to Y/Y2 terminal on furnace control, as
shown in Fig. 31. The 24-v terminal block is marked for easy
connection of field wiring. (See Fig. 36.) The 24-v circuit
contains a 3-amp, automotive-type fuse located on furnace
control. (See Fig. 36.) Any electrical shorts of 24-v wiring during
installation,service, or maintenance may cause fuse to blow. If
fuse replacement is required, use only a fuse of identical size
(3 amp) and type. The control will flash code 24 when fuse
needs replacement.
NOTE: Use AWG No. 18 color-coded copper thermostat wire
for lengths up to 100 ft. (30.4 M). For wire lengths over 100 ft
(30.4 M), use AWG No. 16 wire.
FACTORY
INSTALLED
LOCATION
POWER ENTRY HOLE
FILLER PLUG (FACTORY-
SUPPLIED LOOSE PARTS BAG)
UNUSED 7/8-IN. (22 mm) DIAMETER
POWER ENTRY HOLES
- - 29 - -
FACTORY
INSTALLED
LOCATION
UNUSED 7/8-IN. (22 mm)
DIAMETER POWER
ENTRY HOLES
A05113