Input
LOW NOISE MODE
PEAK CUT MODE
―
―
5-1-1.
EXTERNAL INPUT
ON/OFF of the "Low noise mode" and "Peak cut mode" functions can be specified by external
signal.
LOW NOISE MODE
•
The following reduces the operating sound of the outdoor unit from the normal sound.
The air conditioner is set to the "Low noise mode" by applying the contact input of a commercial
timer or ON/OFF switch to a connector on the outdoor control PC board.
* Performance may drop depending on the outside air temperature condition, etc.
Circuit diagram example
z
•
Use the following parts and construct a circuit like that shown above.
Outdoor unit
control PC board
Connector
Red
1
White
2
Black
3
*10 m
Surely insulate with
insulation tape etc. since
this wire is not used.
* Make the distance from the PC board to the connected unit within 10 m.
•
Input signal∙∙∙ON : Low noise mode / OFF : Normal operation
* Set the "Low noise mode" type by "Push switch" on the outdoor control PC board.
Input signal
Low noise mode
Parts (Optional)
z
Parts name
External connect kit
Output
―
―
ERROR STATUS
COMPRESSOR STATUS
Connected unit
Vcc
Vcc
Power
supply
R
SW
Signal
Field supply
ON
OFF
ON
OFF
Model name
UTY-XWZXZ2
Connector
CN19
CN19
CN18
CN18
1) Power supply
●Voltage (Chart sign=Vcc) : DC 5V to 24V
●The current capacity : About 100mA
2) Switch (Chart sign=SW)
● Toggle switch or Rocker switch, etc : Switch which maintains the
states.
● Prepare switches which are enough capable for DC 10mA
current or more
3) Resistance (Chart sign=R)
●Adjust the resistance for current to about DC 10mA
(Example)
●In case of Vcc=DC 5V : Rated resistance value 470Ω 1/4W
●In case of Vcc=DC 12V : Rated resistance value 1kΩ 1/4W
●In case of Vcc=DC 24V : Rated resistance value 2.2kΩ 1/4W
Wire (External input) : Red / White / Black
- (05-34) -
Remarks
See external
input/output settings