9.
SAFETY DEVICES
Circuit protection
Fan motor protection
Compressor protection
High pressure protection
Low pressure protection
Protection form
Current fuse (Main PCB)
Current fuse (Main PCB)
Current fuse (Main PCB)
Thermal protector
Thermal protection program
(Compressor temp.)
Thermal protection program
(Discharge temp.)
Thermal protection program
(Heat exchanger temp.)
Pressure sensor
Pressure sensor
- (04-17) -
AOÛG36LA
OFF: 150 ± 15 °C
ON: 120 ± 15 °C
ON: After 7 minutes
Cooling
OFF: 4.1 MPa
Heating
ON: After 3 minutes
OFF: 0.12 MPa or less(for 5 minutes)
Cooling
ON: After 7 minutes
Model
AOÛG45LA
AOÛG54LA
250V 5A
250V 3.15A
250V 10A
OFF: 110 °C
ON: 80 °C
OFF: 115 °C
OFF: 68 °C
ON: 63 °C