CLIMAVENETA i-ACCURATE i-AX Installation Manual - User And Maintenance page 62

Precision air-conditioners
Table of Contents

Advertisement

Indication of operating state SQX62
LED
Indication
Green
Lit
Flashing
Red
Lit
Flashing
Both
Dark
2 WAY VALVE CLOSE-OFF
For applications where the 2 way valve is needed, verify the Close Off value in table below if they are suitable with the system. For different
value, make specific request.
FRAME
MODELS i-AT/i-AD
3
4
5
6
7
*close off = Maximum permissible differential pressure at which the motorised valve will close securely against the pressure
62
English 09/10
Function
Control mode
Calibration
Internal error
Calibration error
No power supply
Electronics faulty
2 WAY VALVE CLOSE-OFF
Actuator
29
SSC
50
SSC
70
SSC
90
SSC
130
SQX
Remarks, troubleshooting
Automatic operation; everything o.k.
Wait until calibration is finished
(green or red LED will be lit)
Troubleshooting, eventually replace actuator
Troubleshooting, recalibrate
(operate button S3 1x)
Check mains network, check wiring
Replace actuator
Valve model
KVS
VXP
10
VXP
16
VXP
25
VXP
25
VXG
40
i-ACCURATE i-AX - i-AW - i-AD - i-AT - i-AF
close off* (kPa)
300
175
75
75
300