CLIMAVENETA i-ACCURATE i-AX Installation Manual - User And Maintenance page 12

Precision air-conditioners
Table of Contents

Advertisement

i-ACCURATE INVERTER i-AF, water-cooled
rame
Model
Power supply
Refrigerant
No. of compressors / no. of circuits
CAPACITY DELIVERED (DX)
Maximum speed
Gross total capacity (1)
Gross sensible capacity (1)
SHR (1)
Total compressor power consumption
EER
Minimum speed
Gross total capacity (1)
Gross sensible capacity (1)
SHR (1)
Compressor power consumption
Booster (non-continuous operation)
Gross total capacity (1)
Gross sensible capacity (1)
SHR (1)
Compressor power consumption
WATER CONDENSER PLATE
Type
Q.ty
COOLING CAPACITY (FREE-COOLING)
Total cooling capacity gross (2)
Sensible cooling capacity gross (2)
SHR (2)
Water pressure drop in FC mode
Water connection
Water volume
VENTILATION
Rated air flow
No. of EC radial fans
Power with radial fan
Sound pressure level (5)
Air filter
HUMIDIFIER
Capacity
Power consumption
ELECTRIC HEATERS
Steps
Power consumption
DIMENSIONS
W
D
H
i-BDC outdoor dry cooler (fans with EC motor)
BDC outdoor dry cooler (fans with asynchronous motor)
1 - air 24°C-50%, water 30-35°C - ESP 20Pa
2 - water inlet 10°C and flow-rate same as calculated for DX operation - ESP 20 Pa
5 - Measured at h=1,5 m height and 2 m front in free fie
* PAY ATTENTIONS: PIPELINE DIMENSIONS MUST BE CALCULATED FROM INSTALLED LOCALLY,
FOLLOWING THE INSTRUCTION ON WATER CONNECTIONS PARAGRAPHS
12
English 09/10
F3
F4
29
50
V/Ph/Hz
400/3N/50
400/3N/50
R410A
R410A
1/1
1/1
kW
28,58
53,46
kW
28,35
50,26
0,99
0,94
6,15
13,08
kW
3,60
3,19
kW
12,42
23,24
kW
12,42
23,24
1,00
1,00
kW
1,49
3,79
33,3
56,26
kW
30,47
51,42
kW
0,92
0,91
kW
8,72
14,40
Brazed Plate Condenser AISI316
1
2
24,34
43,5
kW
kW
24,34
43,5
1
1
kPa
65,62
91,31
IN
1"1/2 F
1"1/2 F
1"1/4 M
1"1/4 M
OUT
11,8
19,1
l
mc/h
8000
13500
1
2
kW
1,78
3,69
60
64
dB(A)
G4
G4
kg/h
5
5
kW
3,75
3,75
3
3
9
15
kW
1000
1550
mm
mm
790
790
mm
1980
1980
i-BDC039m i-BDC078m i-BDC103m i-BDC123m i-BRE190m
BDC039m
i-BDC078m
F5
F6
F7
70
90
130
400/3N/50
400/3N/50
400/3N/50
R410A
R410A
R410A
2/2
2/2
3/2
71,36
92,9
128,6
68,52
86,2
110,4
0,96
0,93
0,86
14,73
20,2
28,6
3,55
3,51
3,62
21,18
22,89
24,5
18,89
21,73
24,5
0,89
0,95
1,00
3,82
3,88
3,91
80,3
102,2
/
72,0
90,2
/
0,90
0,9
/
18,3
23,9
/
2
1
1
57,73
78,06
104,5
57,73
78,06
94,07
1
1
0,90
101,17
94,7
132
2" F
2" F
2" F
1"1/4 M
2" M
2" 1/2 M
26,8
32,5
47,8
19000
24000
28000
3
3
3
5,38
6,24
6,90
67
67
67
G4
G4
G4
8
8
15
6
6
11,25
3
3
3
18
18
24
2100
2650
2650
790
790
890
1980
1980
1995+200
BDC103m
BDC123m
BRE190m