INSTALLATION MANUAL
precision air-conditioners
ACCURATE
Direct expansion
Air-cooled
AXO air outlet from the top
AXU air outlet from the bottom
Water-cooled
AWO air outlet from the top
AWU air outlet from the bottom
GB
frame 1:
07-10
frame 2:
15-18
frame 3:
20-26-29
frame 4:
39-30-40-50
frame 5:
55-60-70

Advertisement

Table of Contents
loading

Summary of Contents for CLIMAVENETA ACCURATE AXO

  • Page 1 Библиотека СОК  INSTALLATION MANUAL precision air-conditioners ACCURATE Direct expansion Air-cooled AXO air outlet from the top AXU air outlet from the bottom Water-cooled AWO air outlet from the top AWU air outlet from the bottom frame 1: 07-10 frame 2: 15-18 frame 3: 20-26-29...
  • Page 3 INDEX Documents Front outlet plenum Direct expansion unit configuration Front outlet moulding General characteristics Position and diameter of the water connections 18 Air flows Hot water re-heating Rating plate Water connections General technical data Connection to brazed plate condenser Accessing the main components Correction factors Transport and handling Air condenser: suggested installation...
  • Page 4 DIRECT EXPANSION UNIT CONFIGURATION type digit 9 10 11 12 13 14 15 16 17 18 19 20 21 22 A X O Digit 1 RANGE ACCURATE air-conditioner Climaveneta Version Digit 2 Air-cooled “LT” (low temperature) VERSION Water-cooled Air-cooled Digit 3...
  • Page 5 Digit 11 Mechanical thermostatic valve THERMOSTATIC VALVE Electronic thermostatic valve Digit 12 No post-heating STD heaters with 3 steps HEATING Hot water post-heating coil Hot water post-heating coil + STD heaters with 3 steps Hot gas post-heating coil Hot gas post-heating coil + STD heaters with 3 steps Digit 13 No humidity and condensate management Probe for humidity reading only...
  • Page 6: General Characteristics

    GENERAL CHARACTERISTICS DESCRIPTION OF THE UNIT AIR FLOW SENSOR Ductable precision air-conditioners with capacities from 7 to 70 Activates an alarm in the event of insufficient air flow. kW for vertical installation, cooling only, with the possibility of electric or hot water post-heating, humidifier and dehumidifier COOLING COIL option for the precision control of the temperature-humidity Large front surface, made from copper tubes expanded mechani-...
  • Page 7 AIR-COOLED DIRECT EXPANSION UNIT - VERSION WATER-COOLED DIRECT EXPANSION UNIT - VER- SION AW AW* Refrigerant circuit Refrigerant circuit All models have a single refrigerant circuit, and in some cases two All models have a single refrigerant circuit, and in some cases two circuits.
  • Page 8: Air Flows

    AIR FLOWS The ACCURATE air-conditioners are available in different con- erally have the air intake at the front, rear and/or from the bot- figurations, based on the air intake and outlet positions; the main tom, as required by the customer, and the air outlet from the top distinction is between OVER and UNDER units.
  • Page 9: Rating Plate

    RATING PLATE The air-conditioner rating plate is positioned on a panel inside the unit, and provides the following information: - Model and serial number of the unit; - Power supply (voltage, phases and frequency); MODEL SERIAL NUMBER - Power input of the unit and the individual components; CODE COOLING CAPACITY POTENZA TERMICA...
  • Page 10 ACCURATE AW water cooled Total cooling capacity (1) 18,9 20,8 27,4 30,8 Sensible cooling capacity (1) 14,6 17,2 20,8 27,6 SHR (1) 0,91 0,97 0,95 Total cooling capacity (2) 13,5 18,9 24,7 27,4 Sensible cooling capacity (2) 13,5 16,5 18,9 24,2 26,1 SHR (2)
  • Page 11: Accessing The Main Components

    ACCESSING THE MAIN COMPONENTS The air-conditioner is accessible from all sides by removing the various panels. The front and/or side panels are opened in 2 different ways: FRONT PANELS All the front panels are hinged and fitted with locking latches and seal.
  • Page 12: Transport And Handling

    TRANSPORT AND HANDLING Move the air-conditioner, which must not be reclined or tipped over, nor exposed to the elements, as near as possible to the site of installation before removing the packaging and the pallet. The units can be lifted: - using a forklift, sliding the forks through the openings in the pallet;...
  • Page 13: Dimensions And Weight

    DIMENSIONS AND WEIGHT The values are indicated without tolerances, to the average level of precision required according to UNI EN 22768-1. L (mm) 1000 1000 1550 2100 L1(mm) 1000 1530 2080 H (mm) 1980 1980 1980 1980 1980 H1(mm) 1940 1940 1940 1940...
  • Page 14: Operating Space

    ACCURATE unit Raised floor Elastic gasket Elastic gasket OPERATING SPACE Access is from the front only for all models. This feature ensures easy access to all the main components in the unit for installation and periodical maintenance. Thanks to this feature, the units can be installed next to one another, or alternatively fitted in racks.
  • Page 15 OPTIONAL BASE MOULDING (A*O UNITS) The "OVER" units are designed for the connections to pass through the base of the unit; nonetheless, if there is no raised floor (units with intake from the rear or front), to simplify the connection of the pipes and cables, a base moulding must be used.
  • Page 16 Air outlet for OVER versions sizes: 07-10-15-18 sizes: 20-26-29-39-30-40-50-55-60-70 1000 1000 1550 2100 Air outlet for UNDER versions sizes: 07-10-15-18 sizes: 20-26-29-39-30-40-50-55-60-70 1000 1000 1550 2100 ACCURATE AX* - AW* English 01/07...
  • Page 17 Air intake from the bottom for OVER versions sizes: 07-10-15-18 sizes: 20-26-29-39-30-40-50-55-60-70 1000 1000 1550 2100 Air intake from the top for UNDER versions sizes: 07-10-15-18 sizes: 20-26-29-39-30-40-50-55-60-70 1000 1000 1550 2100 ACCURATE AX* - AW* English 01/07...
  • Page 18 INTAKE PLENUM, UNDER VERSIONS (A*U UNITS) For ducting the air intake, plenums are available to be fitted between the top of the unit and the air return duct or the false- ceiling. NOTE: The standard air filters (EU2/EU4) and optional filters (EU5) are fitted inside the air-conditioner, upstream of the finned coil;...
  • Page 19 FRONT OUTLET PLENUM (A*O UNITS) The figure shows the front outlet plenum (optional for A*O units). L (mm) 1000 1000 1550 2100 P (mm) H (mm) FRONT OUTLET MOULDING (A*U UNITS) The figure shows the moulding for the front air outlet (optional for A*U units).
  • Page 20: Position And Diameter Of The Water Connections

    POSITION AND DIAMETER OF THE WATER CONNECTIONS OVER - UNDER CONNECTIONS sizes 07 - 10 6 0 0 1 4 2 Humidifier connection IN - H2O (water-cooled) IN - Liquid OUT - GAS IN/OUT hot water post-heating OUT - H2O (water-cooled) power supply OVER - UNDER CONNECTIONS sizes 15 - 18...
  • Page 21 OVER - UNDER CONNECTIONS sizes 20 - 26 - 29 IN - humidifier OUT - humidifier IN - H2O (water-cooled) 1 0 0 0 power supply 1 1 4 1 5 0 OUT - GAS 2 2 5 . 5 3 9 8 .
  • Page 22: Hot Water Re-Heating

    OVER - UNDER CONNECTIONS sizes 55 - 60 - 70 IN - humidifier IN - Liquid circ. 1 IN - H2O (water-cooled) circ. 1 IN - H2O (water-cooled) circ. 2 2 1 0 0 OUT - humidifier IN - Liquid circ. 2 power supply IN/OUT hot water 1 1 4...
  • Page 23: Water Connections

    WATER CONNECTIONS For all the water connections (with the exception of the rect. condensate drain), the following are recommended: Insulate all the chilled water pipes with closed cell material - flexible connections to avoid transmitting vibrations and (e.g.: Armaflex or equivalent), to prevent condensation; the allow small movements of the air-conditioner;...
  • Page 24: Air Condenser: Suggested Installation

    AIR CONDENSER: SUGGESTED INSTALLATION 1/100 air-conditioner outlet max 30 metres air-conditioner 1/100 max 5 metres outlet liquid 1/100 max 3 metres max 15 air-conditioner metres max 3 metres N.B.: the liquid pipes must be protected against solar radiation ACCURATE AX* - AW* English 01/07...
  • Page 25: Refrigerant Connections

    REFRIGERANT CONNECTIONS DIAMETERS OF THE CONNECTIONS INSIDE THE UNIT Liquid line (mm) Gas outlet line (mm) RECOMMENDED OUTSIDE DIAMETERS OF THE LINES (for equivalent lengths up to 30m) Liquid line (mm) 12 mm 16 mm 18 mm 2 x 14 mm 2 x 16 mm Gas outlet line (mm) 18 mm...
  • Page 26: Humidifier Power Supply

    HUMIDIFIER POWER SUPPLY Underneath the fill solenoid valve on the steam production unit is position:V-F the threaded male fitting (V) for the humidifier water supply. This is already fitted with a plastic hose, diameter 6 mm, for con- nection to the building's water supply (see figure, point F). V: Steam production unit - inlet connection (threaded male fit- ting);...
  • Page 27 EMPTYING AND CHARGING The refrigerant circuits of the water-cooled chillers and air-condi- with nitrogen (or dry air) to prevent moisture from entering the tioners are already charged with refrigerant, either R407C, R22 circuit; in this case, the refrigerant charge must be completed by or R134a (check the rating plate on the unit and the compressors the installer, following the instructions shown in this paragraph.
  • Page 28: Electrical Specifications

    ELECTRICAL SPECIFICATIONS TOTAL UNIT POWER INPUT Vers. Main Switch mod. V/ph/Hz 400/3N/50 2,47 7,95 6,47 25,45 4,72 17,75 6,47 25,45 400/3N/50 3,22 9,85 7,22 27,35 5,47 19,65 27,35 400/3N/50 5,02 18,1 13,02 53,1 8,77 23,6 12,58 53,1 400/3N/50 5,66 17,8 13,66 52,8 9,41...
  • Page 29 Modulating humidifier models V/ph/Hz n° kg/h 07 - 10 230/1/50 2,25 15 - 18 400/3N/50 3,75 20 - 26 - 29 400/3N/50 3,75 39 - 30 - 40 - 50 400/3N/50 3,75 55 - 60 - 70 400/3N/50 Compressors models V/ph/Hz n°...
  • Page 30: Electrical Connections

    ELECTRICAL CONNECTIONS Correct electrical connection, performed in a workmanlike man- open (position “O”); ner and in compliance with the standards in force, is important The power section of the electrical panel is protected by a plastic for the prevention of accidents and the good and long-lasting screen;...
  • Page 31 ACCURATE AX* - AW* English 01/07...