Removal Of Fan Motor - Daikin Skyair FHC35K Service Manual

Cooling only heat pump split-system air conditioner skyair r(y)k&f series addition of fuy, fvy-l, fay-fa, fhyc140kve models r71, 100kval, r125ktal models
Table of Contents

Advertisement

Si-71A
3.4

Removal of Fan Motor

Procedure
Step
1.
Removing fan motor
a. Disconnect connector
b. Remove lead wire
retaining plate
2.
Remove screws for
mounting fan motor.
∗FUY71FJV1 :
Three screws
∗FUY100/125FJV1 :
Four screws
3.
Remove motor by pulling
down.
Removal Procedure
Warning
Be sure to turn off all power supplies before disassembling work.
Procedure
For FUY71/100/125FJ
Poins
Caution
∗Fan motor can be removed without
removing the lead wire retaining plate.
However, when washing the heat
exchanger, this plate should be
removed and protect the lead wires.
157