Removal Of Fan Rotor And Fan Motor - Daikin Skyair FHC35K Service Manual

Cooling only heat pump split-system air conditioner skyair r(y)k&f series addition of fuy, fvy-l, fay-fa, fhyc140kve models r71, 100kval, r125ktal models
Table of Contents

Advertisement

Si-71A
5.3

Removal of Fan Rotor and Fan Motor

Procedure
Step
Removing fan rotor
1
Turn bell mouth in CW to
remove it.
2
Remove hexagon nut and
turning stopper plate to
disassemble fan rotor.
Removing fan motor
1
Disconnect lead wire for fan
motor and harness for
capacitor from switch box.
2
To dismount pipe-fixing
plate, remove a screw and
slide the plate to left side.
3
To remove wire-fixing plate,
remove two screws and slide
the plate upward.
4
Remove four hexagon head
screws to dismount fan
motor.
Removal Procedure
Warning
Be sure to turn off all power supplies before disassembling work.
Procedure
For FVY71L~125L
Points
Caution
When reassembling be sure to clamp
wires.