Lack Of Gas Malfunction - Daikin Skyair FHC35K Service Manual

Cooling only heat pump split-system air conditioner skyair r(y)k&f series addition of fuy, fvy-l, fay-fa, fhyc140kve models r71, 100kval, r125ktal models
Table of Contents

Advertisement

Si-71A
6.19

Lack of Gas Malfunction

83 83 83 83
Remote Controller
Display
A(H1P) — ýýý 1(H2P) — 2(H3P) —
LED Display
Applicable Models
R(Y)
Method of
Lack of gas is detected according to discharge pipe temperature.
Malfunction
Detection
Malfunction
Microcomputer decides whether there is a lack of gas and detects malfunction.
„ Stop due to malfunction does not occur even though a malfunction is determined to have occurred.
Decision
Conditions
„ Lack of refrigerant
Supposed Causes
„ Refrigerant piping circuit clogging
Troubleshooting
Troubleshooting
Troubleshooting by Remote Controller Display / LED Display
Is the
amount of
NO
refrigerant correct?
YES
Charge with the proper amount
of refrigerant.
Check the refrigerant piping
circuit for clogging.
(SF021)
117