Fuel Factors
An important consideration affecting the entire installation
is the type of fuel used by your generator. The system was
factory tested and adjusted using natural gas, but can be
converted to use LP vapor. For proper engine function,
factors that are inherent to each of these fuels, your location
and the duration of possible utility interruptions are important
considerations in the following fuel guidelines:
particulate material. Using fuels outside the
following recommended values may cause
performance problems.
grade HD5 propane with a minimum fuel energy of
2500 BTUs/ft3 with maximum propylene content of
5% and butane and heavier gas content of 2.5% and
minimum propane content of 90% is required.
Natural gas rating will depend on specific fuel but typical
derates are between 10 to 20% off the LP gas rating.
Natural gas or LP engines are certified to operate on natural
or liquid propane gas. The emissions control system for this
engine is EM (Engine Modifications).

Fuel Pressure

Both LP vapor and natural gas fuel supply pressure at the
generator's fuel inlet port should be between the following
levels at full load with all gas appliances turned on
and operating.
Ensure that all gas line shutoff valves are OPEN and that
adequate fuel pressure is available whenever automatic
operation is desired.

Power Loss

Air density is less at high altitudes, resulting in less available
engine power. Specifically, engine power will decrease 3.5%
for each 1,000 feet (300 meters) above sea level and 1% for
each 10° F (5.6°C) above 77°F (25°C). Make sure you and
your installer consider these factors when determining total
generator load.

Fuel Pipe Sizing

There are numerous on-line or otherwise-published
references for fuel pip sizing. For example, NFPA 54-Natural
Fuel Gas Code, 2006 (Item #: 320-6031-06) is a
common resource.
The installer should consider the specific gravity of gas and
compensate for a nominal amount of restriction from bends,
fittings, etc. If an unusual number of fittings, bends, or other
restrictions are used, refer to federal and local codes
for guidance.

Fuel Consumption

Estimated fuel supply requirements for natural gas and LP
vapor fuels are shown below.
LP Vapor (Propane)
Cu Ft/Hr
Full Load
Gal/Hr (liquid)
BTU/Hr
Cu Ft/Hr
1/2 Load
Gal/Hr (liquid)
BTU/Hr
Cu Ft/Hr
Exercise
Gal/Hr (liquid)
BTU/Hr
Natural Gas
Cu Ft/ Hr
Full Load
BTU / Hr
Cu Ft/ Hr
1/2 Load
BTU / Hr
Cu Ft/ Hr
Exercise
BTU / Hr
Recommended Energy
Content of Fuel
Heating Value:
BTU per gallon (gross**)
Cubic feet (gas)
10 kW
8 kW
65.6
56.4
1.82
1.57
164000
141000
42.8
37.6
1.18
1.04
107000
94000
23.6
20
0.65
0.55
59000
50000
10 kW
8 kW
169
121
169000
121000
111
94
111000
94000
60
53
60000
53000
LP Vapor
Natural
Gas
91,547
2,500
1,000
21