4. Field Settings

4.1

Model Type Setting

ARC466A6
4.2

When 2 Units are Installed in 1 Room

Outline
When 2 indoor units are installed in 1 room, 1 of the 2 indoor units and the corresponding
wireless remote controller can be set for different addresses.
Both the indoor unit PCB and the wireless remote controller need alteration.
Indoor Unit PCB
Wireless Remote
(1) Remove the cover and take it off.
Controller
(2) Cut the address setting jumper.
Trial Operation and Field Settings
This remote controller is common to the heat pump model and cooling only model. Use the
DIP switch on the remote controller to set the heat pump model.
Set the DIP switch to H/P as shown in the illustration. (The factory set is the heat pump
side.)
Cut the address setting jumper JA on the control PCB.
DIP switch
H/P
C/O
(R12275)
JA
ADDRESS
EXIST
1
CUT
2
(R16497)
Jumper
Address
EXIST
1
2
CUT
(R14631)

Field Settings

167