Daikin FTXS20K2V1B Service Manual page 122

Inverter pair wall mounted type k-series
Hide thumbs Also See for FTXS20K2V1B:
Table of Contents

Advertisement

Indoor Unit
Step
3
Pull out the air filter
downward and remove
it.
3. Remove the Titanium
apatite photocatalytic
air-purifying filters.
1
The Titanium apatite
photocatalytic air-
purifying filter is
attached to the back of
the air filter.
2
Remove the Titanium
apatite photocatalytic
air-purifying filter frame
by bending the air filter
and unfastening the
projections from the air
filter frame.
3
Remove the Titanium
apatite photocatalytic
air-purifying filter from
its frame (at 5 positions)
by bending it.
112
Procedure
Titanium apatite
photocatalytic
air-purifying filter
Projection
Hook
Points
(R16658)
Air filter
(R8025)
(R14599)
To prevent the damage, do
not remove the Titanium
apatite photocatalytic air-
purifying filter from the frame
when cleaning it.
The Titanium apatite
photocatalytic air-purifying
filter is not marked for
difference between the right
and left sides.
(R8027)
SiBE041134
Removal Procedure