Massachusetts Requirements - Superior Fireplaces Signature DRT6340TYN Installation Instructions Manual

Signature series 40 and 45 in. power vent direct-vent gas fireplaces
Table of Contents

Advertisement

INNOVATIVE HEARTH PRODUCTS • POWER VENT DV GAS FIREPLACES (DRT63__TYN / DRC63__TYN) • INSTALLATION INSTRUCTIONS
Gas Pressure - All Models
Tables 2 and 3 show the appliance inlet and
manifold gas pressure requirements.
Inlet Gas Supply Pressure
Minimum
5.5" WC
(1.37 kPa)
Table 2
Manifold Gas Supply Pressure
Low
1.6" WC
(.40 kPa)
Table 3
Test gauge connections are provided on the front
of the gas control valve; identified IN for the inlet
and OUT for the manifold side (see Figure 1).
The appliance and its appliance main gas
valve must be disconnected from the gas
supply piping system during any pressure
testing of that system at test pressures in
excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the gas
supply piping system by closing its equipment
shutoff valve during any pressure testing of
the gas supply piping system at test pres-
sures equal to or less than 1/2 psi (3.5 kPa).
Gas Valve Diagram
See Figure 1 for gas valve diagram.
(From DFC Wire
Manifold (Out)
Test Port
Inlet (In) Test Port
Wire
(From DFC Wire
harness)
Main Gas Inlet
3/8" NPT
Figure 1 - SIT Electronic Gas Valve
4
PURGE CYCLE
This is a power vented fireplace that
requires household electrical power
to operate. It will not operate during
a power failure. When the fireplace
is turned off, the exhaust blower will
continue to operate for approximately
Maximum
fifteen (15) seconds after shutdown
10.5" WC
to expel the exhaust gases from the
(2.62 kPa)
venting system.
Orifice Sizes - Sea Level To high Altitude
These appliances are tested and approved for
high
installation at elevations of 0 - 4500 ft (0 - 1370
3.5" WC
m) above sea level, using the standard burner
(.87 kPa)
orifice sizes (marked with an "*" in Table 4).
For elevations above 4500 ft, contact your gas
supplier or qualified service technician.
Deration - At higher elevations, the amount
of BTU fuel value delivered must be reduced
by either:
• Using gas that has been derated by the gas
company.
• Changing the burner orifice to a smaller size
as regulated by the local Authorities Having
Jurisdiction and by the (USA) National Fuel
Gas Code NFPA 54/ANSI Z223.1 - latest
edition, or in Canada, the CAN/CGA-B149.1
code - latest edition.
Install the appliance according to the regulations
of the local authorities having jurisdiction, and
the (USA) National Fuel Gas Code NFPA 54 /
ANSI Z223.1 - latest edition,
or (Canada) CAN/CGA-B149.1 - latest edition.
NOTE: Flame appearance will diminish 4%
per one thousand feet of altitude.
Green Wire
harness)
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Table 4
In Canada - CAN/CGA-2.17-M91 (R2009) (high
altitude):
ThE CONVERSION ShALL BE CARRIED OUT
BY A MANUFACTURER'S AUThORIZED REP-
RESENTATIVE, IN ACCORDANCE WITh ThE
REQUIREMENTS OF ThE MANUFACTURER,
PROVINCIAL OR TERRITORIAL AUThORITIES
hAVING JURISDICTION AND IN ACCORDANCE
WITh ThE REQUIREMENTS OF ThE CAN/CGA-
B149.1 OR CAN/CGA-B149.2 INSTALLATION
CODES.
REQUIREMENTS FOR ThE COMMON-
WEALTh OF MASSAChUSETTS
These fireplaces are approved for installation in
the US state of Massachusetts if the following
additional requirements are met:
• Install this appliance in accordance with
Massachusetts Rules and Regulations 248
C.M.R.
• Installation and repair must be done by a
plumber or gas fitter licensed in the Com-
monwealth of Massachusetts.
• The flexible gas line connector used shall
not exceed 36 in. (92 centimeters) in length.
• The individual manual shut-off must be a
T-handle type valve.
Massachusetts horizontal Vent Requirements
In the Commonwealth of Massachusetts, hori-
zontal terminations installed less than seven
(7) feet above the finished grade must comply
with the following additional requirements:
Connect GTMS
Wire harness
• A hard wired carbon monoxide detector
with an alarm and battery back-up must be
installed on the floor level where the gas
Pressure
fireplace is installed. The carbon monoxide
Regulator
detector must comply with NFPA 720, be
Tower
ANSI/UL 2034 listed and be ISA certified.
• A metal or plastic identification plate must
be permanently mounted to the exterior of
the building at a minimum height of eight (8)
Yellow Ground Wire
feet above grade and be directly in line with
(From DFC Wire
the horizontal termination. The sign must
harness)
read, in print size no less than one-half (1/2)
inch in size, GAS VENT DIRECTLY BELOW.
KEEP CLEAR OF ALL OBSTRUCTIONS.
Burner Orifice Size
Elevation 0 - 4500 ft (0 - 1370 m)
Model
Orifice Size / Catalog Number
40 in.
0.125" (1/8") * H7924 •
45 in.
0.136" (#29) * H8141 •
* Standard size installed at factory
• Part /Cat. Number