Inspection; Prepare The Appliance For Inspection; Carry Out A Visual Check For General Signs Of Corrosion; Gas Valve Leakage Test - Buderus Logamax plus GB162-L.B. 80 kW Installation Instructions Manual

Condensing gas boiler
Table of Contents

Advertisement

11

Inspection

11
Inspection
Offer your customer an annual inspection and maintenance contract.
The activities to be included in an annual inspection and maintenance
contract can be found in the inspection ( § 15.2, page 57) and service
reports ( § 15.3, page 57).
WARNING:
Do not use this boiler if any part has been under water.
▶ Immediately call a qualified service technician to
inspect the boiler and to replace any part of the
control system and any gas control which has been
under water.
CAUTION:
Insufficient or improper cleaning and maintenance can
cause damage to the installation.
▶ Inspect and clean the appliance once a year.
▶ Carry out maintenance as required. Immediately
remedy faults. This will avoid further damage to the
system!
CAUTION:
Risk of electric shock.
▶ Before opening the appliance:
▶ disconnect the appliance from the power supply
using the appliance emergency OFF button or
disconnect the relevant circuit breaker of the house
from the power grid.
▶ Secure the appliance against accidental restarting.
▶ Periodically examine the venting systems and cleaning of the screens
in the vent terminal.
▶ Also periodically inspect the low water cutoffs, including flushing of
float types and clean the condensate collections and disposal
system.
11.1

Prepare the appliance for inspection

INSTRUCTION FOR THE INSTALLER
▶ If gas pipes have to be disconnected from the gas
burner fitting, the burner cover must only be opened
by a specialized professional.
▶ Switch OFF the appliance by pressing the main switch of the BC10.
▶ Close the gas valve [1].
42
▶ Close the isolating valves [2].
Fig. 76 Closing the valves (here: in closed position)
▶ Open the boiler door:
– Turn the vent key through a quarter rotation to undo the boiler
door lock ( fig. 77, step 1).
– Push the fastener down ( fig. 77, step 2) and open the boiler
door.
NOTICE
▶ If the boiler door cannot be opened completely,
remove it ( § 12.2, page 43).
3
4
Fig. 77 Opening the boiler door
11.2
Carry out a visual check for general signs of
corrosion
▶ Check all gas and water-bearing pipes for signs of corrosion and for
leaks.
▶ Replace any pipes that are corroded.
▶ Carry out a visual inspection of the burner, heat exchanger,
condensate trap, automatic air vent and all fittings in the boiler.
11.3

Gas valve leakage test

▶ Check the internal tightness of the gas fitting on the input side (with
the boiler switched OFF) at a test pressure of 7.0" W.C. (17.4 mbar)
for natural gas and 8.0" W.C. (19.9 mbar) for LPG.
▶ Check that the appliance is switched OFF.
▶ Open the screw plug on the testing nipple for the gas connection by
2 turns ( fig. 78, [1]).
Logamax plus GB162-L.B. 80 kW / 100 kW – 6720645916 (2014/10)
1
2
6720645916-75.1N
1
2
6720645916-76.1N

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents