Adjust Blower Off Delay (Heat Mode); Set Thermostat Heat Anticipator; Check Safety Controls; Checklist - Bryant 352MAV Installation, Start-Up, And Operating Instructions Manual

Series b, 2-stage, direct vent condensing gas furnace
Table of Contents

Advertisement

THERMOSTAT SUBBASE
TERMINALS WITH
THERMOSTAT REMOVED
R Y W G
10 TURNS
FROM UNIT 24-VOLT
TERMINAL BLOCK
5.0 AMPS ON AMMETER
EXAMPLE:
10 TURNS AROUND JAWS
Fig. 56—Amp Draw Check with Ammeter
When using an electronic thermostat, set cycle rate for 3 cycles per
hour.
V. CHECK SAFETY CONTROLS
This section covers the safety controls that must be checked before
the installation is complete. The flame sensor, gas valve, and
pressure switch were all checked in the Start-up Procedure section
as part of normal operation.
1. Check Primary Limit Control
This control shuts off combustion control system and
energizes air-circulating blower motor if furnace overheats.
Recommended method of checking this limit control is to
gradually block off return air after furnace has been
operating for a period of at least 5 minutes. As soon as limit
control has shut off burners, return-air opening should be
unblocked to permit normal air circulation. By using this
© 2002 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231
HOOK-AROUND
VOLT/AMMETER
= 0.5 AMPS FOR THERMOSTAT SETTING
A80201
method to check limit control, it can be established that
limit is functioning properly and operates if there is a
restricted return-air supply or motor failure. If limit control
does not function during this test, cause must be determined
and corrected.
2. Check Pressure Switch
This control proves operation of draft inducer. Check
switch operation as follows:
a. Turn off 115-v power to furnace.
b. Remove outer furnace door and disconnect inducer
motor lead wires from wire harness.
c. Turn on 115-v power to furnace.
d. Set thermostat to "call for heat" and wait 1 minute. When
pressure switch is functioning properly, hot surface
igniter should not glow, and control diagnostic light
flashes a Status Code 32. If hot surface igniter glows
when inducer motor is disconnected, shut furnace down
immediately. Determine reason pressure switch did not
function properly and correct condition.
e. Turn off 115-v power to furnace.
f. Reconnect inducer motor leads, reinstall main furnace
door, and turn on 115-v power supply.
VI. CHECKLIST
1. Put away tools and instruments. Clean up debris.
2. Check SW-1 through SW-3 after completing installation to
ensure desired settings for thermostat type (SW-1) and
blower-OFF delay (SW-2 and SW-3).
3. Verify manual reset switch has continuity.
4. Verify that blower and outer doors are properly installed.
5. Cycle test furnace with room thermostat.
6. Check operation of accessories per manufacturer's instruc-
tions.
7. Review User's Guide with owner.
8. Leave literature packet near furnace.
—46—
Printed in U.S.A.
352m602
Catalog No. 5335–204

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents