Upper Collector Box And Inducer Housing (Unused) Drain Connections; Condensate Trap Freeze Protection; Downflow Applications; Condensate Trap Location - Bryant 352MAV Installation, Start-Up, And Operating Instructions Manual

Series b, 2-stage, direct vent condensing gas furnace
Table of Contents

Advertisement

G. Upper Collector Box and Inducer Housing (Unused)
Drain Connections
1. Upper collector box drain connection
Attached to the UPPER collector box drain connection is a
factory-installed corrugated, plugged tube (blue and white
striped label). This tube is plugged to prevent condensate
leakage in this application. Ensure this tube is plugged.
NOTE: See Fig. 6 or 7 or tube routing label on main furnace door
to check for proper connections.
2. Upper inducer housing drain connection
Attached to the UPPER (unused) inducer housing drain
connection is a cap and clamp. This cap is used to prevent
condensate leakage in this application. Ensure this connec-
tion is capped.
NOTE: See Fig. 6 or 7 or tube routing label on main furnace door
to check for proper connections.
H. Condensate Trap Freeze Protection
Refer to Condensate Drain Protection section for recommenda-
tions and procedures.
III. DOWNFLOW APPLICATIONS
In a downflow furnace application, the blower is located above the
burner section, and conditioned air is discharged downwards.
COLLECTOR BOX
DRAIN TUBE (BLUE)
CAP
PLUG
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX
EXTENSION TUBE
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR BOX
EXTENSION TUBE
CONDENSATE
TRAP
INDUCER HOUSING
DRAIN TUBE (VIOLET)
Fig. 8—Downflow Tube Configuration
Left-Hand Trap Installation)
A. Condensate Trap Location
The condensate trap must be removed from the factory-installed
blower shelf location and relocated in selected application location
as shown in Fig. 2, 8, or 9.
To relocate condensate trap from the blower shelf to desired
location, perform the following:
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs
inward and rotating trap.
DRAIN TUBE
COUPLING
Fig. 9—Downflow Tube Configuration
3. Remove casing hole filler cap from casing hole. (See Fig. 2,
7, or 8.)
4. Install casing hole filler cap into blower shelf hole where
trap was removed.
5. Install condensate trap into desired casing hole by inserting
tube connection stubs through casing hole and rotating until
tabs snap into locking position.
B. Condensate Trap Tubing
NOTE: See Fig. 8 or 9 or tube routing label on main furnace door
to check for proper connections.
Relocate tubes as described below.
1. Collector Box Drain Tube
a. Remove factory-installed plug from LOWER collector
box drain tube (blue and white striped label).
b. Install removed clamp and plug into UPPER collector
box drain tube (blue label) which was connected to
condensate trap.
c. Connect LOWER collector box drain connection to
condensate trap.
(1.) Condensate Trap Located on Left Side of Casing
A01023
(2.) Condensate Trap Located on Right Side of Casing
—8—
(Right-Hand Trap Installation)
(a.) Connect LOWER collector box drain tube
(blue and white striped label) to condensate
trap. Tube does not need to be cut.
(b.) Clamp tube to prevent any condensate leakage.
(a.) Install drain tube coupling (factory-supplied in
loose parts bag) into collector box drain tube
(blue and white striped label) which was pre-
viously plugged.
(b.) Connect larger diameter drain tube (factory-
supplied in loose parts bag) to drain tube
coupling, extending collector box drain tube
for connection to condensate trap.
PLUG
CAP
COLLECTOR BOX
DRAIN TUBE (BLUE)
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX
EXTENSION TUBE
COLLECTOR BOX
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR BOX
EXTENSION TUBE
INDUCER HOUSING
DRAIN TUBE
(VIOLET)
CONDENSATE
TRAP
COLLECTOR BOX
EXTENSION
DRAIN TUBE
A01024

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents