Adjustments; Set Temperature Rise; Blower Off Delay (Heat Mode); Set Thermostat Heat Anticipator - Bryant 345MAV Installation, Start-Up, And Operating Instructions Manual

4-way multipoise fixed-capacity condensing gas furnace series b
Table of Contents

Advertisement

c. Measure time (in sec) for gas meter test dial to complete
1 revolution.
d. Refer to Table 9 for cu ft of gas per hr.
e. Multiply gas rate (cu ft/hr) X heating value (Btu/cu ft)
using natural gas heating value from local gas
utility/supplier.
TABLE 9—GAS RATE (CU FT/HR)
SECONDS
SIZE OF TEST DIAL
1
2
5
FOR 1
REVOLUTION
cu ft
cu ft
cu ft
10
360
720
1800
11
327
655
1636
12
300
600
1500
13
277
555
1385
14
257
514
1286
15
240
480
1200
16
225
450
1125
17
212
424
1059
18
200
400
1000
19
189
379
947
20
180
360
900
21
171
343
857
22
164
327
818
23
157
313
783
24
150
300
750
25
144
288
720
26
138
277
692
27
133
267
667
28
129
257
643
29
124
248
621
30
120
240
600
31
116
232
581
32
113
225
563
33
109
218
545
34
106
212
529
35
103
206
514
36
100
200
500
37
97
195
486
38
95
189
474
39
92
185
462
40
90
180
450
41
88
176
439
42
86
172
429
43
84
167
419
44
82
164
409
45
80
160
400
46
78
157
391
47
76
153
383
48
75
150
375
49
73
147
367
EXAMPLE:
Btu heating input = Btu/cu ft X cu ft/hr
Heating value of gas = 975 Btu/cu ft
Time for 1 revolution of 2-cu ft dial = 70 sec
Gas rate = 103 cu ft/hr (from Table 9)
Btu heating input = 103 X 975 = 100,425 Btuh
In this example, the orifice size and manifold pressure
adjustment is within 2 percent of the furnace input
rate.
B. Set Temperature Rise
CAUTION: Temperature rise must be within limits
specified on unit rating plate. Recommended operation is
at midpoint of rise or above. Failure to follow this caution
may result in condensing or overheating the heat ex-
changers.
Determine and adjust air temperature rise as follows:
1. Place thermometers in return and supply ducts as close to
furnace as possible. Be sure thermometers do not see heat
exchanger so that radiant heat does not affect readings. This
practice is particularly important with straight-run ducts.
SECONDS
SIZE OF TEST DIAL
1
2
5
FOR 1
REVOLUTION
cu ft
cu ft
cu ft
50
72
144
360
51
71
141
355
52
69
138
346
53
68
136
340
54
67
133
333
55
65
131
327
56
64
129
321
57
63
126
316
58
62
124
310
59
61
122
305
60
60
120
300
62
58
116
290
64
56
112
281
66
54
109
273
68
53
106
265
70
51
103
257
72
50
100
250
74
48
97
243
76
47
95
237
78
46
92
231
80
45
90
225
82
44
88
220
84
43
86
214
86
42
84
209
88
41
82
205
90
40
80
200
92
39
78
196
94
38
76
192
96
38
75
188
98
37
74
184
100
36
72
180
102
35
71
178
104
35
69
173
106
34
68
170
108
33
67
167
110
33
65
164
112
32
64
161
116
31
62
155
120
30
60
150
2. When thermometer readings stabilize, subtract return-air
temperature from supply-air temperature to determine air
temperature rise.
3. Adjust temperature rise by adjusting blower speed. Increase
blower speed to reduce temperature rise. Decrease blower
speed to increase temperature rise.
WARNING: Disconnect 115-v electrical power before
changing speed tap. Failure to follow this warning could
result in personal injury.
4. To change blower motor speed selections for heating mode,
remove blower motor lead from control center HEAT
terminal. (See Fig. 27.) Select desired blower motor speed
lead from 1 of the other terminals and relocate it to HEAT
terminal. See Table 10 for lead color identification. Recon-
nect original lead on SPARE terminal.
Follow this same procedure for proper COOL speed selec-
tion.
TABLE 10–SPEED SELECTOR
COLOR
Black
Yellow (When Present)
Blue
Red
White
C. Blower Off Delay (Heat Mode)
The main blower off time delay period is factory-set at 135 sec and
is not field-adjustable.
D. Set Thermostat Heat Anticipator
Thermostat heat anticipator must be set to match amp draw of
components in R-W circuit. Accurate amp draw measurements can
be obtained at thermostat subbase terminals R and W.
Fig. 42 illustrates an easy method of obtaining these measure-
ments. Amp reading should be taken after blower motor has
started. See thermostat manufacturer's instructions for adjusting
heat anticipator and for varying heating cycle length.
THERMOSTAT SUBBASE
TERMINALS WITH
THERMOSTAT REMOVED
10 TURNS
5.0 AMPS ON AMMETER
EXAMPLE:
10 TURNS AROUND JAWS
Fig. 42—Amp Draw Check with Ammeter
—38—
FACTORY-
SPEED
SHIPPED
CONNECTION
High
Medium High
Medium Low
Low
Common
HOOK-AROUND
VOLT/AMMETER
R Y W G
FROM UNIT 24-VOLT
TERMINAL BLOCK
= 0.5 AMPS FOR THERMOSTAT SETTING
Cool
Spare
Heat
Spare
Com
A80201