Panasonic S-36PU1E5A Technical Data & Service Manual page 371

R410a models
Hide thumbs Also See for S-36PU1E5A:
Table of Contents

Advertisement

SELECTING THE LOCATION FOR THE INDOOR UNIT
5-1. Required Minimum Space for Installation and Service
Provide a check port on the piping side ceiling for repair and maintenance.
Install the indoor unit once the following conditions are satisfied and after receiving the customer approval.
1.
The indoor unit must be within a maintenance space.
2.
The indoor unit must be free from any obstacles in path of the air inlet and outlet, and must allow spreading of air
throughout the room.
Top view
(Uint : mm)
Inspection hole
(600 x 600)
600
<Front>
If the height from the floor to ceiling exceeds three meters, air flow distribution deteriorates and the effect is decreased.
POSITION OF SUSPENSION BOLT
A
B
Table 1-11
TYPE
A
B
S-36PN1E5A
S-45PN1E5A
840
780
S-50PN1E5A
S-60PN1E5A
1060
1000
S-71PN1E5A
S-100PN1E5A
1260
1200
S-125PN1E5A
S-140PN1E5A
Front view
Control box
600
Unit: mm
C
D
E
523
64
650
523
64
650
523
64
650
Above 250cm
Apply a joint-canvas between the unit and duct to
absorb unnecessary vibration.
Install the unit leaning to a drainage hole side as a
figure for easy water drainage.
CAUTION
Remove the absorber at air
return hole before installation.
Absorber
1-361
Fig. 1-108
1 ~ 3mm
Drainage hole
Fig. 1-109