1) Indoor Air Temperature Control
By the control method, not only the thermostat is switched on and off, as explained section "4-12-1".
Indoor Air Temperature Control ", but also the frequency of the compressor's inverter is controlled in
accordance with
When
T is high (not yet reached the temperature set
with the remote controller).
When
T is low (approximately +1.0 or less in the
cooling mode or approximately -1.0 or more in the
heating mode).
When the indoor air temperature is rising in the cooling
mode and dropping in the heating mode.
When the indoor air temperature is dropping in the
cooling mode and rising in the heating mode.
*
The fluctuations of the compressor inverter frequency adjustments are calculated taking into account not only
but also fluctuations in indoor air temperature.
4
2) Maximum and Minimum Frequency Control
The compressor's inverter frequency is controlled in accordance with the model and operation mode.
The maximum and minimum frequencies for each model are shown in the table below.
* There are cases in which frequency is limited with other control functions depending on operational conditions,
so operations are not always carried out in accordance with the maximum frequencies listed below.
· Maximum and minimum frequency
Maximum Frequency (Hz)
Minimum Frequency (Hz)
* There is a case in which the frequency is set at 24.0Hz to protect the compressor in accordance with ambient
temperature and indoor loads.
3) Current Release Control
The inverter frequency is controlled so that the current value for the inverter compressor is less than the figure
listed in the table below in order to prevent abnormal increases in the inverter circuit located within the outdoor
unit's electrical box.
Current release control with primary current : The limited values are modified in accordance with ambient
Cooling
Is (A)
Heating
NOTE
The limited values are lowered under the following conditions.
Cooling : ambient temperature > 40°C
Heating : ambient temperature > 10°C
T and fluctuations in indoor air temperature. Inverter frequency is controlled as follows:
50PE
Cooling
87.0
Heating
108.0
Cooling
15.0*
Heating
15.0*
temperature.
50PE
60PEY
71PEY
10.2
15.0
15.0
12.0
18.0
18.0
Controlled so that the inverter frequency is increased.
Controlled so that the inverter frequency is decreased
or kept.
Controlled so that the inverter frequency is increased.
Controlled so that the inverter frequency is decreased.
60PEY
71PEY
93.0
98.0
99.0
103.2
15.0*
15.0*
15.0*
15.0*
4-12