LOCATING YOUR U31/I31 FIREPLACE
Due to high temperatures the Insert should be located out of traffic and away
from furniture and draperies. Provide a minimum of 48" (1220mm) front
clearance to the unit.
This appliance is Listed for bedroom installations when used with a Listed
Millivolt Thermostat. Some areas may have further requirements, check local
codes before installation.
This unit is not approved for installation into a mobile home.
ASH LIP FOR FLUSH INSTALLATION
a)
An ashlip is mandatory on a U31/I31 Flush (flat window) Insert when installed less than 6" (152mm), (including the
4"(102mm) Hearth Trim) to a combustible floor (see Figure 1). For detailed installation see Faceplate and Trim Installation.
Note: If the ashlip is required with the Flush Front installed, the bottom Gold Trim will NOT fit and cannotbe installed.
b)
No ashlip is required when U31/I31 Insert is raised by 2"(51mm). See figure 2.
c)
No ashlip is required on a U31/I31 Insert with a Bay Window and/or Bay Louvers. See figure 3.
Figure 1
U31/I31 Gas Insert Zero Clearance Kit
Figure 3