Clearances To Combustibles; Combustible Mantel Clearances - Regency U31 Owners & Installation Manual

Gas insert zero clearance kit
Hide thumbs Also See for U31:
Table of Contents

Advertisement

INSTALLATION
The clearances for the Zero Clearance Kit are 0" to combustibles (back, side and floor) but when planning your installation
review the clearances required for the Insert (see below) after it is installed in the Zero Clearance Kit. The Zero Clearance Kit
must be installed on a flat, solid, continuous surface (e.g. wood, metal, concrete). This may be the floor, or raised up on a platform
to enhance its visual impact.
NOTE: The specified '0' inch floor clearance means that the top surface of the flooring material, i.e. carpeting, tile, etc.,
must not extend above the bottom edge of the 4" Hearth Trim.
From Unit
Sides
A
Drop Ceiling
B
12" Mantel*
C(My) 22" / 555 mm
From Surround
Sides
D
Drop Ceiling
E
Max. Mantel Depth*
G(Mx) 12" / 305 mm
Max. Alcove Depth
H
Min. Alcove Width
J
Facing (Mantel Leg)
Side**
K
Top
L
K
D
A
Top View
**Max. width of 1"(25mm) at 1"(25mm) from surround, calcu-
late depth at 45
o
as shown in the diagram.
4

CLEARANCES TO COMBUSTIBLES

Clearances to Combustibles for Insert
10" / 250 mm
47.5" / 1207 mm
2" / 50 mm
37.75" / 945 mm
36" / 882mm
48" / 1200 mm
1" / 25 mm
1" / 25 mm
45
K
Max.
K
* Mantel clearances vary with the width of the mantel see
the chart "Combustible Mantel Clearances" on this page.
Note:
A non- combustible mantel may be installed at a
lower height if the framing is made of metal studs
covered with a non- combustible board.
Side View

*Combustible Mantel Clearances

Depth (Mx)
(inches)
(mm)
0" to 3.5"
0mm to 89mm
to 5.5"
to 140mm
to 12"
to 305mm
U31/I31 Gas Insert Zero Clearance Kit
Clearance (My)
(inches)
(mm)
20"
508mm
21"
533mm
22"
559mm