Viessmann VITOTRONIC 200 Service Instructions Manual page 88

Vitotronic 200 type wo1a heat pump control unit
Table of Contents

Advertisement

Troubleshooting
Diagnosis (service scans)
Line "I [–]"
Col-
Explanation
umn
4
Protection functions for control of hot gas superheating (C/D)
C Characteristics of the external
unit:
"0"
Standard mode, protection
function disabled.
"1"
Compressor frequency is
reduced slowly.
"2"
Compressor frequency will
not be reduced further.
"3"
Compressor frequency will be
increased.
Line "Nload, f [–, Hz]"
Col-
Explanation
umn
2
Standardised output demand, value range: 0 to 127 (≙ 0 to 100 %)
3
Current compressor frequency in Hz.
4
Set compressor frequency in Hz.
Line "n1, n2 [rpm]"
Col-
Explanation
umn
2
Speed of fan 1 in rpm.
3
Speed of fan 2 in rpm (if installed).
4
Set fan stage:
"0"
OFF
"1"
Low speed
"2"
Medium speed
Line "OAT, OMT, OCT [°C]"
Col-
Explanation
umn
2
Air intake temperature, evaporator (OAT)
3
Evaporation temperature (OMT)
4
Refrigeration inlet temperature, evaporator (OCT)
88
(cont.)
D Cause:
"0"
Standard mode.
"1"
Set value for hot gas super-
heating cannot be achieved by
adjusting position of EEV
valve.
"3"
High speed
"4"
Max. speed

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vitotronic 200 wo1a

Table of Contents