Viessmann VITOTRONIC 200 Service Instructions Manual page 152

Vitotronic 200 type wo1a heat pump control unit
Table of Contents

Advertisement

PCBs and connection options
Main and extension PCB
Information regarding the connection
values
■ The output given is the recommended
connected load.
■ The stated current indicates the max.
switching current of the switching con-
tact (observe the total current for all
connected components of 5 A).
Plug fÖ
Terminals
Function
Internal power supply of the
PCBs.
Plug sYÖ
Terminals
Function
210.1
/
End of the safety chain.
210.2
/
Compressor control stage 1
direct or via EEV controller
(refrigerant circuit control).
152
(cont.)
:
:
Explanation
Factory connection.
Explanation
'Live' in case of fault-free safety chain.
Factory connection
■ Heat demand: Contact closed, 210.2
is 'live'.
■ If the compressor will not start, check
whether it has been enabled by the
EEV controller (own relay on EEV
PCB).