Service And Detector Test Accessories - Bosch FAP-DO420 Operation Manual

Automatic fire detectors lsn improved version
Hide thumbs Also See for FAP-DO420:
Table of Contents

Advertisement

28
en | Accessories
CAUTION!
If the current consumption for the connected detector exceeds 20 mA, it can lead to the
malfunction of or damage to the MPA.
You should restrict the maximum detector current consumption to 20 mA to avoid damaging
the MPA.
NOTICE!
The cable length between the detector and the MPA must not exceed 3 m when connected by
an unshielded cable.
MPA technical specifications
Operating voltage
Maximum current consumption
Display medium
Permissible wire gauge
Dimensions
Weight
VdS approval number
6.8

Service and Detector Test Accessories

SOLO200 Detector Removal Tool
The pivoting grips and three different diameters make
the SOLO200 Detector Removal Tool suitable for
removing and replacing most fire detectors.
The plastic caps enable the fire detector to be securely
gripped and protect the detector surface against
damage.
RTL-cap plastic caps for the SOLO200 Detector
Removal Tool
Scope of delivery = 2 pieces
F.01U.003.448 | 8.0 | 2011.10
Terminal 2
Terminal 3
Terminal 4
Operation Guide
Automatic Fire Detectors LSN improved
9 V DC to 30 V DC
approx. 2 mA
limited to approximately 13 mA
limit to maximum 20 mA
1 LED
0.6 mm. . . 0.8 mm
79 x 79 x 31 mm
Approx. 65 g
G 294 052
Bosch Sicherheitssysteme GmbH
version

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents