20
en | Connection
5.4

Detector Base Sounders

Detector base sounders are used if acoustic alarm signaling is required directly at the fire
source. Detector base sounders are available in four variants.
The integrated tone generator has 11 tones for selection
(incl. tones conforming to DIN 33404 and EN 457) with
sound pressure of max. 100 dBA, depending on the type of
tone selected.
With the LSN variants, the volume (4 levels) and also the
tone type are programmed via the fire panel. The tone type
on conventional variants is set via four DIP switches and the
volume is adjusted continuously via a potentiometer.
FNM-420-A-BS Detector Base Sounder White or Red, for LSN
line technology, with power supply via the LSN with 32
different tones
5.5

Installation of the Detector Module

NOTICE!
The packaging for the multisensor detector with C sensor consists of tear-proof PE-ALU
laminated film and must be cut open carefully.
After installation and connection of the base, the detector head is set into the base and
turned to the right as far as it will go.
Detector bases are delivered with inactive locks.
The detector module can be locked in the base (removal protection). The locking feature is
activated by breaking the bolt (X) out of the base and pushing it into the corresponding guide,
as shown in Figure 5.1.
F.01U.003.448 | 8.0 | 2011.10
MSS 300 Detector Base Sounder White, for
conventional line technology, activation via the C point
of the detector in use.
MSS 300 WS-EC Detector Base Sounder White, for
conventional line technology, with external activation
(via an interface module).
MSS 401 Detector Base Sounder White, for LSN line
technology, with separate power supply.