Automatic Fire Detectors LSN improved
version
8.1
Notes for the Service
NOTICE!
The DO detectors are not supported by the WinPara programming software.
NOTICE!
With the exception of the special KKW detector types, you can use the WinPara programming
software (V 4.53 or higher) to display the serial number, contamination level, operating hours
and current analog values for all configured detectors.
8.1.1
Display of Operating Data in WinPara
Module Address
Module where the detector or detector line is installed.
Address
Detector installation address, e.g. 10-03: The detector is in zone 10 and is the detector
number 3.
Brief Info
Additional information entered during programming. e.g. "FAP-O 420 on MSS400" means that
the FAP-O 420 is installed together with an MSS 400 Detector Base Sounder. You can also
enter the position of the detector here.
Type
display of the set detector type.
Serial number
The first digit of the 8-digit serial number represents the year of manufacture, i.e. a detector
with the serial number 3931859 was manufactured in 2003.
Current analog values
Optical system value (display of the current contamination value):
0 . . . 170
0 . . . 350
350 . . . 450
450 . . . 510
From 511 O fault: optical sensor is deactivated!
Bosch Sicherheitssysteme GmbH
Initial set-up value for a new detector
Normal working range
Slight contamination: Exchange detector soon
Heavy contamination: Exchange detector immediately
Operation Guide
Maintenance and Service | en
F.01U.003.448 | 8.0 | 2011.10