Analog fire panels
2.8

Notification Appliance Circuit Devices

Two Class A or Class B Notification Appliance Circuits (NACs) provide up to 4 A of 24 V power
(maximum 2.5 A on each circuit) to operate horns, strobes, bells, and other notification
appliances. Each NAC can be programmed to provide Temporal Code 4, Temporal Code 3, and
Steady, Pulsing, and synchronized output for Wheelock, System Sensor, and Gentex
notification appliances.
For a list of compatible notification appliances, see the FPA-1000 NAC Compatibility List
available as a PDF at www. boschsecurity.com.
For UL approved notification patterns, see UL 864 Standard-specific Requirements, page 43.
2.9

Communicator

Each FPA‑1000 has a dual phone line PSTN/DACT circuit and an Ethernet connection featuring
Conettix IP reporting. The panel communicates in Contact ID, SIA, and Modem IIIa
The panel provides miscellaneous reporting functions such as dialing control and transmission
supervision, priorities of report groups, routing to destinations, manual and auto test reports,
and Anti-Replay feature.
For the primary and secondary account, the following features are programmable:
With modem function, it is possible to program the control panel remotely (upload a new
parameter file to the panel from a remote station).
Compatible Device for the PSTN/DACT Circuit and Ethernet Connection
Designation
D6600
D6100i
Tab. 2.10: Compatible PSTN/DACT and Ethernet devices
2.10

Components and Accessories

For semi-flush mounting of the control panel cabinet, the FPM‑1000‑SFMK Semi-flush
Mounting Kit with trim ring is available.
The D5070 Analog point programmer provides easy programming of Signaling Line Circuit
device addresses.
Alternatively to the complete FPA-1000 Fire panel, you can order separate components. The
FPA‑1000-LC includes the mainboard with keypad. The FPM-1000-ENC includes the enclosure
with the dead front door.
Type Number
FPM-1000-SMK
Bosch Security Systems, Inc.
Two different phone numbers or IP addresses, or one phone number and one IP address
Different dialing types for PSTN (pulse only, tone and pulse, or tone only)
Individual PSTN line supervision (audible and visible trouble signal in the case of a
transmission path failure)
Selectable options for Report Steering Groups
Programmable supervision time for each Conettix IP reporting account
Test call frequency individually programmable for each account (4-, 6-, 24-hour, 7- and 28-
day intervals
Description
Communications Receiver/Gateway
Communications Receiver/Gateway
Description
Semi-flush Mounting Kit
Includes trim ring and mounting accessories.
Installation and Operation Guide
System information | en
21
2
.
2017.11 | 2.0 | F.01U.173.607