TABLE 6 - ELECTRICAL DATA
POWER
MODEL
SUPPLY
208/230-3-60
DCG180
460-3-60
575-3-60
208/230-3-60
DCG240
460-3-60
575-3-60
10
COMPRESSORS
COND. FAN
MOTORS
#1
#2
(#1 & #2)
HP
RLA LRA RLA LRA
EACH
38.4 248 19.2 124
1
19.2 124
9.6
62
1
15.4 100
7.7
50
1
38.4 248 38.4 248
1
19.2 124 19.2 124
1
15.4 100 15.4 100
1
SUPPLY AIR
BLOWER
MOTOR
FLA
HP
FLA
EACH
4.1 / 4.2
5
15.4 / 14.4
2.1
5
7.2
2.0
5
5.9
4.1 / 4.2
7.5
21.0 / 19.4
2.1
7.5
9.7
2.0
7.5
7.8
VOLTAGE
LIMITATIONS**
**Utilization Range "A" in accordance with ARI Standard 110.
MINIMUM
MAXIMUM
CIRCUIT
TIME DELAY
AMPACITY
FUSE SIZE
(AMPS)
(AMPS)
87.1 / 84.9
100
42.4
50
33.9
40
115.1 / 111.6
125
55.8
60
44.8
50
VOLTAGE
POWER SUPPLY
MIN.
208/230-3-60
187
460-3-60
414
575-3-60
518
Unitary Products Group
MAX.
253
506
630

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

D2cg180D2cg240