TABLE 3: NATURAL GAS APPLICATION DATA
AVAILABLE ON MODELS
2-1/2 & 3 TON
2-1/2 TON
3 TON
3-1/2 TON, 4 & 5 TON
3 TON
3-1/2 TON
4 & 5 TON
4 & 5 TON
1.
Heating capacity valid for elevations up to 2000 feet above sea level. For elevations above 2,000 feet, rated capacity should be reduced by 4% for
each 1,000 feet above sea level.
3
2.
Based on 1075 BTU/Ft.
3.
The air flow must be adjusted to obtain a temperature rise within the range shown. Continuous return air temperature should not be below 55°F.
1
TABLE 4: PROPANE
(LP) GAS APPLICATION DATA
INPUT CAPACITY
AVAILABLE ON
MODELS
2-1/2 & 3 TON
2-1/2 TON
3 TON
3-1/2, 4 & 5 TON
3 TON
3-1/2 TON
4 & 5 TON
4 & 5 TON
1.
Propane applications are accomplished by field installation of a Propane Conversion Accessory, Model 1NP0807 for 2-1/2 and 3 ton units with
33-1/2" tall cabinets and Model 1NP0808 for 3-1/2 thru 5 ton units with 41-1/2" tall cabinets.
2.
Heating capacity valid for elevations up to 2,000 feet above sea level. For elevations above 2,000 feet, rated capacity should be reduced by 4% for
each 1,000 feet above sea level.
3
3.
Based on 2500 BTU/Ft.
4.
The air flow must be adjusted to obtain a temperature rise within the range shown. Continuous return air temperatures should not be below 55°F.
Unitary Products Group
OUTPUT
INPUT CAPACITY
CAPACITY
1
(MBH)
45
70
70
80
90
108
108
135
.
OUTPUT CAPACITY
2
(MBH)
(MBH)
45
36
70
56
70
56
80
64
90
72
108
87
108
87
135
108
.
2
GAS RATE
3
FT.
/HR.
(MBH)
36
42
56
65
56
65
64
74
72
84
87
100
87
100
108
126
3
GAS RATE
3
FT.
/HR.
18
28
28
32
36
43
43
54
TEMP. RISE °F AT FULL
NUMBER OF
INPUT
BURNERS
MIN.
2
25
3
30
3
25
3
25
4
30
4
45
4
30
5
35
TEMP. RISE °F AT FULL
NUMBER OF
INPUT
BURNERS
MIN.
2
25
3
30
3
25
3
25
4
30
4
45
4
30
5
35
3
MAX.
55
60
55
55
60
75
60
65
4
MAX.
55
60
55
55
60
75
60
65
7