Clearances; Duct Work; Roof Curb; Filters - York DNH 030 Installation Manual

Affinity series single packaged gas/electric air cooled air conditioners
Hide thumbs Also See for DNH 030:
Table of Contents

Advertisement

282911-YIM-B-0807
TABLE 2: UNIT WEIGHTS AND CENTER OF
GRAVITY
SHIPPING
OPERATING
UNIT
WEIGHT
WEIGHT
SIZE
(LBS.)
(LBS.)
030
395
036
400
042
470
048
475
060
485
FRONT
OF
UNIT
"A"
49-1/8
25
FIGURE 2 -

UNIT CENTER OF GRAVITY

CLEARANCES

All units require certain clearances for proper operation and
service. Refer to Table 10 for the clearances required for
combustion, construction, servicing and proper unit opera-
tion.
Do not permit overhanging structures or shrubs to
obstruct the condenser air discharge, combustion
air inlet or vent outlet.

DUCT WORK

These units are adaptable to downflow use as well as rear
supply and return air duct openings. To convert to downflow,
use the following steps:
1.
Remove the duct covers found in the bottom return and
supply air duct openings. There are four (4) screws
securing each duct cover (save these screws to use
later).
2.
Install the duct covers, removed in step one, to the rear
supply and return air duct openings. Secure with the four
(4) screws used in step one.
Unitary Products Group
CORNER WEIGHTS
(LOCATION, LBS.)
"A"
"B"
"C"
390
98
95
96
395
100
96
98
465
131
129
101
470
133
130
102
480
136
133
105
"D"
CENTER OF
GRAVITY
"C"
47-1/4
"B"
25
3.
Seal duct covers with silicone caulk.
Duct work should be designed and sized according to the
methods of the Air Conditioning Contractors of America
(ACCA), as set forth in their Manual D.
"D"
A closed return duct system shall be used. This shall not pre-
clude use of economizers or ventilation air intake. Flexible
99
joints may be used in the supply and return duct work to min-
101
imize the transmission of noise.
103
104
107
When fastening duct work to the side duct flanges
on the unit, insert the screws through the duct
flanges only. Do not insert the screws through the
casing. Outdoor ductwork must be insulated and
waterproofed.
NOTE: Be sure to note supply and return openings.
Refer to Figure 9 for information concerning rear and bottom
supply and return air duct openings.

ROOF CURB

On applications when a roof curb is used, the unit must be
positioned on the curb so the front of the unit is tight against
the curb.

FILTERS

A filter rack and a high velocity filters are standard.
Filters must always be used and must be kept clean. When
filters become dirt laden, insufficient air will be delivered by
the blower, decreasing your units efficiency and increasing
operating costs and wear-and-tear on the unit and controls.
Filters should be checked monthly especially since this unit is
used for both heating and cooling.

CONDENSATE DRAIN

A condensate trap is recommended to be installed in the con-
densate drain. The plumbing must conform to local codes.
Use a sealing compound on male pipe threads. Install the
condensate drain line (NPTF) to spill into an open drain.

SERVICE ACCESS

Access to all serviceable components is provided by the fol-
lowing removable panels:
Blower compartment
Gas control/electrical service access
5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dnh 048Dnh 036Dnh 060Dnh 042

Table of Contents