Trane RAUC-IOM-15 Installation & Maintenance Instructions Manual page 58

Remote split system units air cooled condensing units and evp chillers
Table of Contents

Advertisement

Table 5-8
80 Ton Pressure Curve for each Circuit
400
380
360
340
320
300
280
260
240
220
200
180
55
60
To Check Operating Pressures
1. Start the unit and allow the pressures to stabilize.
2. Measure the outdoor air dry bulb temperature (F)
entering the condenser coil.
3. Measure the discharge and suction pressure (psig)
next to the compressor.
100 Ton Pressure Curve for each Circuit
400
380
360
340
320
300
280
260
240
220
200
180
55
60
To Check Operating Pressures
1. Start the unit and allow the pressures to stabilize.
2. Measure the outdoor air dry bulb temperature (F)
entering the condenser coil.
3. Measure the discharge and suction pressure (psig)
next to the compressor.
COOLING CYCLE PRESSURE CURVE
(Based on Indoor Airflow of 400 CFM / Ton)
FULL LOAD
65
70
75
80
SUCTION PRESSURE, PSIG
4. Plot the outdoor dry bulb temperature and the
operating suction pressure (psig) onto the chart.
5. At the point of intersection, read to the left for the
discharge pressure. The measured discharge
pressure should be within ± 7 psig of the graph.
COOLING CYCLE PRESSURE CURVE
(Based on Indoor Airflow of 400 CFM / Ton)
FULL LOAD
65
70
75
80
SUCTION PRESSURE, PSIG
4. Plot the outdoor dry bulb temperature and the
operating suction pressure (psig) onto the chart.
5. At the point of intersection, read to the left for the
discharge pressure. The measured discharge
pressure should be within ± 7 psig of the graph.
System Start-up (Continued)
115 F OD Ambient
105 F OD Ambient
95 F OD Ambient
85 F OD Ambient
75 F OD Ambient
65 F OD Ambient
85
90
95
100
115 F OD Ambient
105 F OD Ambient
95 F OD Ambient
85 F OD Ambient
75 F OD Ambient
65 F OD Ambient
85
90
95
100
58
105
105