Table 3-1A
Typical Unit Weights & Point Loading Data
Unit
Fin
Operating
Size
Material
Weight
C80
AL
5500
CU
6099
D10
AL
6472
CU
7272
D12
AL
7000
CU
8199
Note:
1. Mounting locations correlate with those shown in point loading illustration.
Table 3-1B
Typical EVP Chiller Weights & General Data
Chiller
Shipping Operating
Size
Weight
Weight
80 Ton
875
1,205
100 Ton
960
1,230
120 Ton
1,150
1,535
* - Refrigerant change is approximate and for the evaporator chiller only.
** - Tube Pull given is the length of the evaporator.
Figure 3-3
Rigging and Center-of-Gravity Data
Unit Weight on Isolator @ Mounting Location
Location 1
2
3
855
557
835
926
629
909
1010
656
983
1104
752
1083
1100
694
1075
1241
838
1225
No. of Ref.
Capacity
Circuits
(Gallons) Charge (Lbs.)*
2
43.1
2
35.0
2
47.9
Installation (Continued)
4
5
6
544
830
541
618
906
616
639
979
636
738
1080
736
678
1071
676
827
1222
825
Refrigerant
Tube Pull
(inches)**
26.5
95
33.4
95
40.4
95
Shipping
Unit
Weight
Size
(Max. Lbs)
C80
5995
79.1
D10
7160
104.2
D12
8052
104.7
L I F T I N G A N D M O V I N G I N S T R U C T I O N S !
DO NOT USE CABLES (CHAINS OR SLINGS) EXCEPT AS
SHOWN. OTHER LIFTING ARRANGEMENTS MAY CAUSE
EQUIPMENT DAMAGE OR SERIOUS PERSONAL INJURY.
EACH OF THE CABLES (CHAINS OR SLINGS) USED TO LIFT
UNIT MUST BE CAPABLE OF SUPPORTING THE ENTIRE
WEIGHT OF THE UNIT.
LIFTING CHAINS (CABLES OR SLINGS) MAY NOT BE THE
SAME LENGTH. ADJUST AS NECESSARY FOR EVEN
LEVEL LIFT.
USE SPREADER BARS AS SHOWN IN DIAGRAM. REFER
TO INSTALLATION MANUAL OR NAMEPLATE FOR UNIT
WEIGHT. REFER TO INSTALLATION INSTRUCTIONS
LOCATED INSIDE CONTROL PANEL FOR FURTHER
RIGGING INFORMATION.
15
7
8
810
528
890
605
951
618
1058
721
1046
660
1206
815
Location of Center of
Gravity =
X
Z
In
mm
In
mm
2009
34.5
876.3
2647
34.6
878.8
2659
34.4
873.8