Snow Accumulation - Lennox G61MPV Service Manual

G61mpv series units
Hide thumbs Also See for G61MPV:
Table of Contents

Advertisement

If Intake and Exhaust Pipe is less than 12 in. (305 mm)
above snow accumulation or other obstructions,
field fabricated piping must be installed.
8" (203 mm) Min. for 2" (51 mm) & 3" (76 mm) DIA. pipe
WALL SUPPORT*
12" (305 mm) Max. for 2" (51 mm) Dia. Exhaust
20" (508 mm) Max. for 3" (76 mm) Dia. Exhaust
6" (152 mm)
Maximum
INTAKE
AIR
É É É É É É É É É É É É
É É É É É É É É É É É É
12" (305 mm) Max. for 2" (51 mm) Dia. Exhaust
20" (508 mm) Max. for 3" (76 mm) Dia. Exhaust
If Intake and Exhaust Pipe is less than 12 in. (305 mm)
above snow accumulation or other obstructions,
field fabricated piping must be installed.
WALL SUPPORT*
12" (305 mm) Max. for 2" (51 mm) Dia. Exhaust
20" (508 mm) Max. for 3" (76 mm) Dia. Exhaust
6" (152 mm)
Maximum
INTAKE
AIR
É É É É É É É É É É É É
É É É É É É É É É É É É
12" (305 mm) Max. for 2" (51 mm) Dia. Exhaust
20" (508 mm) Max. for 3" (76 mm) Dia. Exhaust
WALL TERMINATION KITS (CLOSE−COUPLE)
EXTENDED VENT FOR GRADE CLEARANCE
2 inch (51 mm) 22G44 (US)
3 inch (76 mm) 44J40 (US)
between the end of the exhaust pipe and intake pipe
EXHAUST
12" (305 mm) Minimum
8" (203 mm) Min.
Above Grade or Average

Snow Accumulation

WALL TERMINATION KITS (CLOSE−COUPLE)
EXTENDED VENT FOR GRADE CLEARANCE
2 inch (51 mm) 30G28 (WTK Canada)
3 inch (76 mm) 81J20 (WTK Canada)
See Installation Instructions for additional information.
6" (152 mm)
Minimum
12" (305 mm) Minimum
6" (152 mm)
Above Grade or Average
Minimum
Snow Accumulation
LARGER VENT PIPE SIZE TO TERMINATION
AIR
INTAKE
AIR
5" (127 mm)
É É É É É É É É É É É É
GRADE
É É É É É É É É É É É É
*Use wall support every 24" (610). Use two supports if
extension is greater than 24" but less than 48".
FIGURE 40
REDUCER MAY BE REQUIRED TO ADAPT
LARGER VENT PIPE SIZE TO TERMINATION
EXHAUST
AIR
INTAKE
AIR
5" (127 mm)
GRADE
É É É É É É É É É É É É
É É É É É É É É É É É É
*Use wall support every 24" (610). Use two supports if
extension is greater than 24" but less than 48".
FIGURE 41
Page 63
FIELD−PROVIDED
REDUCER MAY BE REQUIRED TO ADAPT
12"
(305 mm)
FOAM INSULATION
EXHAUST
12" (305 mm) Minimum
Above Grade or Average
5−1/2"
Snow Accumulation
(140 mm)
FIELD−PROVIDED
12"
(305 mm)
FOAM INSULATION
EXHAUST
12" (305 mm) Minimum
5−1/2"
Above Grade or Average
(140 mm)
Snow Accumulation
1/2" (13 mm)
(Field Furnished)
AIR
GRADE
1/2" (13 mm)
(Field Furnished)
AIR
GRADE

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents