SPECIFICATIONS

Installation Requirements

Wolf cooktop ventilation hoods are recommended for
use with Wolf induction, electric and gas cooktops and
integrated modules. For ranges and rangetops, a Wolf pro
ventilation hood is recommended.
These hoods have a telescopic chimney flue. A flue exten-
sion is available through an authorized Wolf dealer.
Installation of the cooktop hood should be 30"
36"
from the bottom of the hood to the countertop.
(914)
Wall and island hoods require an internal, in-line or remote
blower assembly, avail able through an authorized Wolf
dealer. For local dealer information, visit the find a show-
room section of our website, wolfappliance.com.
Consult a qualified HVAC professional for specific installa-
tion and ducting applications.
RATING PLATE
Rating plate location.
|
4
Wolf Customer Care 800.222.7820
Electrical
Installation must comply with all applicable electrical codes.
For wall hoods, locate the electrical supply within the
shaded area shown in the illustration below. Allow a
minimum 12"
hoods, locate the electrical supply on the ceiling inside the
top of the hood. Allow a minimum 6'
connection. A separate circuit, servicing only this appliance
to
(762)
is required.
ELECTRICAL REQUIREMENTS
Electrical Supply
Service
LOCATE
ELECTRICAL
WITHIN
SHADED AREA
18"
(457)
30"
(762) TO
Electrical location—all wall hoods.
Romex
®
wire for connection. For island
(305)
(1.8 m)
grounded, 110/120 VAC, 60 Hz
15 amp dedicated circuit
E
36"
(914) BOTTOM EDGE TO COUNTERTOP
Romex
®
wire for