Check Safety Controls - Bryant 311AAV Series 100 Installation, Start-Up, And Operating Instructions Manual

Single-stage induced combustion deluxe 4-way multipoise furnace
Table of Contents

Advertisement

d. Check and verify orifice size in furnace. NEVER AS-
SUME THE ORIFICE SIZE. ALWAYS CHECK AND
VERIFY.
e. Turn off all other gas appliances and pilots.
f. Jumper R to W/W1.
g. Let furnace run for 3 minutes in low-heat operation.
h. Measure time (in sec) for gas meter to complete 1
revolution. Note reading.
i. Refer to Table 9 for cu ft of gas per hr.
j. Multiply gas rate cu ft/hr by heating value (Btu/cu ft).
NOTE: Measured gas input must be within ± 2 percent of that
stated on furnace rating plate when installed at sea level or derated
at higher altitudes.
k. Remove jumper across R and W thermostat connections
to terminate call for heat.
EXAMPLE: (4300 ft altitude)
Furnace input from rating plate is 88,000 Btuh.
Btu heating input = Btu/cu ft X cu ft/hr
Heating value of gas = 850 Btu/cu ft
Time for 1 revolution of 2-cu ft dial = 85 sec
Gas rate = 85 cu ft/hr (from Table 9)
Btu heating input = 85 X 850 = 72,250 Btuh. In this
example, the orifice size and manifold pressure adjustment
is within ±2 percent of the furnace input rate.
7. Set temperature rise
The furnace must operate within the temperature rise range
specified on the furnace rating plate. Determine the air
temperature as follows:
a. Place thermometers in return and supply ducts as close to
furnace as possible. Be sure thermometers do not see
heat exchangers so that radiant heat does not affect
readings. This practice is particularly important with
straight-run ducts.
b. When thermometer readings stabilize, subtract return-air
temperature from supply-air temperature to determine
air temperature rise.
c. Adjust temperature rise by adjusting blower speed.
Increase blower speed to reduce temperature rise. De-
crease blower speed to increase temperature rise.
WARNING: Disconnect 115-v electrical power before
changing speed tap. Failure to follow this warning could
result in personal injury.
d. To change blower motor speed selections for heating
mode, remove blower motor lead from control HEAT
terminal. (See Fig. 22.) Select desired blower motor
speed lead from 1 of the other terminals and relocate it
to HEAT terminal. See Table 10 for lead color identifi-
cation. Reconnect original lead on SPARE terminal.
8. Follow procedure in 5d for selection of COOL and FAN
speeds.
CAUTION: Recheck temperature rise. It must be within
limits specified on the rating plate. Recommended opera-
tion is at the midpoint of rise or above.
9. Set thermostat heat anticipator
TABLE 9—GAS RATE (CU FT/HR)
SECONDS
SIZE OF TEST DIAL
FOR 1
1
REVOLUTION
Cu Ft
10
360
11
327
12
300
13
277
14
257
15
240
16
225
17
212
18
200
19
189
180
20
21
171
22
164
23
157
24
150
25
144
26
138
27
133
28
129
29
124
30
120
31
116
32
113
33
109
34
106
35
103
36
100
37
97
38
95
39
92
40
90
41
88
42
86
43
84
44
82
45
80
46
78
47
76
48
75
49
73
TABLE 10–SPEED SELECTION
COLOR
White
Black
Yellow
Orange†
Blue
Red
* Continuous-blower speed-as shipped default
† Available on 5–speed blowers only.
a. When using a nonelectric thermostat, the thermostat
heat-anticipation must be set to match the amp draw of
the electrical components in the R-W circuit. Accurate
amp draw readings can be obtained at the wires normally
connected to thermostat subbase terminals, R and W.
Fig. 34 illustrates an easy method of obtaining actual
amp draw. The amp reading should be taken after blower
motor has started and furnace is operating. Connect
ammeter wires as shown in Fig. 34. The thermostat
anticipator should NOT be in th circuit while measuring
current. If thermostat has no subbase, the thermostat
must be disconnected from R and W wires during current
measurement. See thermostat manufacturer's instruc-
tions for adjusting heat-anticipator.
b. When using an elctronic thermostat, set cycle rate for 3
cycles per hr.
V. CHECK SAFETY CONTROLS
The flame sensor, gas valve, and pressure switch were all checked
in the start-up procedure section as part of normal operation.
1. Check Primary Limit Control
—25—
SECONDS
SIZE OF TEST DIAL
2
5
FOR 1
1
Cu Ft
Cu Ft
REVOLUTION
Cu Ft
720
1800
50
72
655
1636
51
71
600
1500
52
69
555
1385
53
68
514
1286
54
67
480
1200
55
65
450
1125
56
64
424
1059
57
63
400
1000
58
62
379
947
59
61
360
900
60
60
343
857
62
58
327
818
64
56
313
783
66
54
300
750
68
53
288
720
70
51
277
692
72
50
267
667
74
48
257
643
76
47
248
621
78
46
240
600
80
45
232
581
82
44
225
563
84
43
218
545
86
42
212
529
88
41
206
514
90
40
200
500
92
39
195
486
94
38
189
474
96
38
185
462
98
37
180
450
100
36
176
439
102
35
172
429
104
35
167
419
106
34
164
409
108
33
160
400
110
33
157
391
112
32
153
383
116
31
150
375
120
30
147
367
SPEED
AS SHIPPED
Common
BLW
High
COOL
Med-High
SPARE
Med
SPARE
Med-Low
HEAT
Low*
FAN
2
5
Cu Ft
Cu Ft
144
360
141
355
138
346
136
340
133
333
131
327
129
321
126
316
124
310
122
305
120
300
116
290
112
281
109
273
106
265
103
257
100
250
97
243
95
237
92
231
90
225
88
220
86
214
84
209
82
205
80
200
78
196
76
192
75
188
74
184
72
180
71
178
69
173
68
170
67
167
65
164
64
161
62
155
60
150

Advertisement

Table of Contents
loading

Table of Contents