Bryant 312AAV L Series Service And Maintenance Procedures Manual

Gas-fired induced - combustion furnace

Advertisement

NOTE: Read the entire instruction manual before starting the
installation.
These procedures are for size 90,000 Btuh input unit.
SAFETY CONSIDERATIONS .....................................................1
INTRODUCTION ..........................................................................1
General ......................................................................................1
PROCEDURE ................................................................................2
CARE AND MAINTENANCE.....................................................2
Cleaning And/Or Replacing Air Filter.....................................2
Blower Motor and Wheel.........................................................3
Cleaning Heat Exchanger .........................................................4
Electrical Controls and Wiring.................................................5
WIRING DIAGRAMS...................................................................8
TROUBLESHOOTING .................................................................8
REGISTERED QUALITY SYSTEM
SAFETY CONSIDERATIONS
Installing and servicing heating equipment can be hazardous due to
gas and electrical components. Only trained and qualified
personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions
such as cleaning and replacing air filters. Observe precautions in
the literature, on tags, and labels attached to or shipped with the
unit and other safety precautions that may apply.
Follow all safety codes. In the United States, follow all safety
codes including the National Fuel Gas Code (NFGC) NFPA
54-1999/ANSI Z223.1-1999. In Canada, refer to the CAN/CGA-
B149.1- and .2-M95 National Standard of Canada, Natural Gas
and Propane Installation Codes (NSCNGPIC). Wear safety glasses
and work gloves. Have fire extinguisher available during start-up
and adjustment procedures and service calls.
This is the safety-alert symbol
the furnace and in instructions or manuals, be alert to the potential
for personal injury.
Understand the signal words DANGER, WARNING, CAUTION,
and NOTE. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies a hazard
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.
service and
maintenance procedures
GAS-FIRED
INDUCED-COMBUSTION FURNACE
CERTIFIED
®
. When you see this symbol on
Cancels: New
Fig. 1-Model 312AAV Multipoise
WARNING: The ability to properly perform mainte-
nance on this equipment requires certain knowledge,
mechanical skills, tools, and equipment. If you do not
possess these, do not attempt to perform any maintenance
on this equipment other than those procedures recom-
mended in the User's Manual. FAILURE TO FOLLOW
THIS WARNING COULD RESULT IN POSSIBLE
DAMAGE TO THIS EQUIPMENT, SERIOUS PER-
SONAL INJURY, OR DEATH.
CAUTION: Label all wires prior to disconnection when
servicing controls. Wiring errors can cause improper and
dangerous operation.
I. GENERAL
These instructions are written as if the furnace is installed in an
upflow application. An upflow furnace application is where the
blower is located below the combustion and controls section of the
furnace, and conditioned air is discharged upward. Since this
furnace can be installed in any of the 4 positions shown in Fig. 2,
you must revise your orientation to component location accord-
ingly.
-1-
312AAV
Series L

INTRODUCTION

SP04-68
11-00
A00353

Advertisement

Table of Contents
loading

Summary of Contents for Bryant 312AAV L Series

  • Page 1: Table Of Contents

    service and 312AAV maintenance procedures Series L GAS-FIRED INDUCED-COMBUSTION FURNACE Cancels: New SP04-68 11-00 NOTE: Read the entire instruction manual before starting the installation. These procedures are for size 90,000 Btuh input unit. TABLE OF CONTENTS SAFETY CONSIDERATIONS .............1 INTRODUCTION ................1 General ..................1 ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS PROCEDURE ................2...
  • Page 2: Electrostatic Discharge (Esd) Precautions Procedure

    AIRFLOW WARNING: Never store anything on, near, or in contact with the furnace, such as: 1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners, or other cleaning tools. 2. Soap powders, bleaches, waxes or other cleaning compounds, plastic or plastic containers, gasoline, UPFLOW kerosene, cigarette lighter fluid, dry cleaning fluids, or other volatile fluids.
  • Page 3: Blower Motor And Wheel

    OUTER DOOR MOUNTING SCREWS VENT ELBOW RATING PLATE PRESSURE SWITCH DRAFT FLUE SAFEGUARD SWITCH COLLECTOR MAIN LIMIT SWITCH GAS MANIFOLD GAS VALVE GAS BURNER MANUAL RESET LIMIT SWITCHES FLAME SENSOR HOT SURFACE BLOWER DOOR IGNITER SAFETY SWITCH CONTROL BLOWER, MOTOR AND CAPACITOR A00342 Fig.
  • Page 4: Cleaning Heat Exchanger

    NOTE: If the heat exchangers get a heavy accumulation of soot g. Remove blower wheel from housing. and carbon, they should be replaced rather than trying to clean CAUTION: The blower wheel should not be dropped or them thoroughly. A build-up of soot and carbon indicates that a bent as balance will be affected.
  • Page 5: Electrical Controls And Wiring

    NOTE: A releasing agent such as PAM cooking spray or equiva- lent (must not contain corn or canola oil, aromatic or halogenated hydrocarbons or inadequate seal may occur) and RTV sealant (G.E. 162, 6702, or Dow-Corning 738) are needed before starting installation.
  • Page 6 FIELD 24-VOLT WIRING FIELD 115-, 208/230-, 460-VOLT WIRING FACTORY 24-VOLT WIRING FACTORY 115-VOLT WIRING NOTE 2 1-STAGE THERMOSTAT FIVE FIELD-SUPPLIED TERMINALS WIRE FUSED DISCONNECT THREE-WIRE 208/230- OR HEATING- 460-VOLT ONLY THREE PHASE 208/230- W/W1 VOLT NOTE 1 SINGLE Y/Y2 115-VOLT FIELD- JUNCTION PHASE SUPPLIED...
  • Page 7 —7—...
  • Page 8: Wiring Diagrams

    SETUP SWITCHES TWINNING AND/OR LOW-HEAT ONLY AND COMPONENT TEST BLOWER OFF-DELAY TERMINAL ACRDJ - AIR CONDITIONING RELAY DISABLE JUMPER 24-V-THERMOSTAT TERMINALS TEST/TWIN TRANSFORMER 24-VAC CONNECTIONS 0.5-AMP024 VAC HUMIDIFIER TERMINAL (24-VAC 0.5 AMP MAX.) PL1 - LOW VOLTAGE MAIN FUSE 3-AMP HARNESS CONNECTOR 3-AMP FUSE SEC-1...
  • Page 9 SERVICE If status code recall is needed, briefly remove then reconnect one main limit wire to display stored status code. LED CODE STATUS CONTINUOUS OFF - Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2. CONTINUOUS ON - Control has 24VAC power. RAPID FLASHING - Line voltage (115VAC) polarity r eversed.
  • Page 10 —10—...
  • Page 11 —11—...
  • Page 12 —12— © 2000 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231 Printed in U.S.A. SP0468 Catalog No. 5331-201...