Bryant 311AAV Series 100 Installation, Start-Up, And Operating Instructions Manual page 23

Single-stage induced combustion deluxe 4-way multipoise furnace
Table of Contents

Advertisement

Fig. 28–Dual Fuel Thermostat with Single-Stage Furnace
and Single-Speed Heat Pump
Fig. 30–Two-Stage Thermostat with Single-Stage Furnace
and Two-Speed Air Conditioner
A00272
Fig. 29– Dual Fuel Thermostat with Single-Stage Furnace
1. Heat pump MUST have a high pressure switch for dual fuel
applications.
2. Refer to outdoor equipment Installation Instructions for additional
information and setup procedure.
3. Select the "ZONE" position on the two-speed heat pump control.
4. Outdoor Air Temperature Sensor must be attached in all dual fuel
applications.
5. Dip switch No. 1 on Thermidistat should be set in OFF position
for air conditioner installations. This is factory default.
6. Dip switch No. 1 on Thermidistat should be set inON position for
heat pump installations.
7. Dip switch No. 2 on Thermidistat should be set in OFF position
for single-speed compressor operation. This is factory default.
8. Dip switch No. 2 on Thermidistat should be set in ON position for
two-speed compressor operation.
A00274
9. Configuration Option No. 10 "Dual Fuel Selection" must be
turnedON in all dual fuel applications.
10. NO connection should be made to the furnace HUM terminal
when using a Thermidistat.
11. The RVS Sensing terminal "L" should not be connected. This is
internally used to sense defrost operation.
12. DO NOT SELECT the "FURNACE INTERFACE" or "BAL-
ANCE POINT" option on the two-speed heat pump control board.
This is controlled internally by the Thermidistat/Dual Fuel Ther-
mostat.
13. Dip switch D on Dual Fuel Thermostat should be set in OFF
position for single-speed compressor operation. This is factory
default.
14. Dip switch D on Dual Fuel Thermostat should be set in ON
position for two-speed compressor operation.
—23—